4.3  Wiring with a mounted and connected safety switch 

Disassemble the lateral panel of the unit using a 13 mm wrench. Connect the supply lead to the safety 

switch (cable glands are provided) according to the label affixed to the unit. Perform a start-up test lasting 

a few seconds in order to check the direction of rotation of the fan. If the direction of rotation is incorrect, 
invert 2 phases (three-phase motors). Nb. in the case of two-speed motors, check the direction of rotation 

of the fan for the two speeds. Close the safety switch's enclosure and re-assemble the lateral panel of the 

unit.

4.4  Wiring with control panel (used in France)

Connect the supply lead to the control panel according to the instructions that come with this device (cable 
glands are provided). Perform a start-up test lasting a few seconds in order to check the direction of rota-
tion of the fan. If incorrect, invert 2 phases on the supply terminal block of the control panel (three-phase 
motor). 

If a comfort-smoke extract control panel is used, see the instructions that come with this device.

4.5  Electrical connection of pressure switch

If the pressure switch is factory assembled, it is fitted to the inside of the unit on the motor side. Open the 

lateral panel of the unit and then the hood located on the pressure switch. Connect the 2 connection cable 
threads. Adjust the triggering value of the pressure switch. Close the hood of the pressure switch and then 
the lateral panel of the unit.

5.  START-UP

In order to start up the fan, make sure that the whole unit, including fan, motor and transmission, rotates 
freely and that there is no object that may be projected by the fan. The unit must be connected to the air 

flow network and the lateral panels must be closed. The machine must be attached to its stand before 

being power is applied.

Switch on just an instant to check the direction of rotation of the turbine.

WARNING: The impeller rotating direction must correspond to each speed in the direction indi-

cated by the arrow on the product. A centrifugal backward fan unit with an impeller that does not 

rotate in the right direction still creates a lowrate and a low pressure in the duct. An incorrect ro-

tating direction can lead to an abnormal overheating of the motor, resulting in its destruction and 

cancelling our manufacturer’s warranty.

If the rotating direction is incorrect, cut off the electrical power supply, make sure no power is pre

-

sent, and then reverse the two power supply phases at the level of the motor’s terminal box for the 

three-phase motors, or make sure that the mains network connection conforms to the schematic 

diagram of § "4. ELECTRICAL CONNECTION", page 11 for the single-phase motors.

While running, make sure that the motor’s absorbed current is not more than 5% above the name plate 
indicated current.
Once the installation and tests have ended, present the main points of the operating and maintenance 
manual to the user; the following should be explained:

•  How to start up and shut down the device.
•  How to change the operating modes.

Then hand over to the user with the technical instructions for use of the casing and assembled accessories 
(control panel, etc.) so that they can be accessed at all times.

Summary of Contents for KDTA-R F400

Page 1: ...10121 INSTRUCTION MANUAL INSTALLATION WIRING COMMISSIONING MAINTENANCE AFNOR CERTIFICATION ISO 14001 Environnement AFNOR CERTIFICATION ISO 9001 Q u a l i t KDTA R F400 F400 120mn extraction fan unit B...

Page 2: ...Handling 10 3 5 Casing assembly 10 4 ELECTRICAL CONNECTION 11 4 1 Preliminary precautions 11 4 2 Wiring without any safety switch 12 4 3 Wiring with a mounted and connected safety switch 13 4 4 Wirin...

Page 3: ...g units are designed for smoke extraction and ventilation applications in residential buildings commercial buildings industrial and logistics buildings and covered car paks Interior or exterior instal...

Page 4: ...to the replacement are the responsibility of the Customer Excluded from our warranty are defects linked to abnormal use or not in accordance with the recommendations in our instructions defects observ...

Page 5: ...1036 1078 1071 926 800 900 509 353 184 471 753 28 125 450 1761 1734 1191 1119 1162 1143 1130 900 1000 570 381 184 486 825 39 182 500 1919 1891 1387 1222 1264 1340 1180 900 1000 640 467 249 521 964 39...

Page 6: ...6 16 NT00000439 KDTA F400 KDTR F400 AN 210121 3 2 Accessory assembly diagrams AVRZ RCAZ TPKD VSKZ RRKZ RCAZ RCAZ PPVZ TPKD RCRZ RCAZ PPHZ VSKZ RRKZ TPKD RCAZ VSKZ RRKZ...

Page 7: ...630 806 466 355 457 304 710 900 510 400 509 328 AxA E Exhaust side bird proof guard Model AVRZ Exhaust side bird proof guard Model AVRZ Exhaust side bird proof guard A E A E 200 260 50 450 572 50 250...

Page 8: ...ular connection Outlet A D A D 200 260 355 450 572 710 250 326 400 500 642 800 280 364 500 560 720 900 315 410 500 630 808 1000 355 459 560 710 902 1250 400 511 630 B C A External roof Model TPKD Exte...

Page 9: ...with pressure than a KDTR backward curved fan KDTA F400 RRKZ Pstat Pa Qv m3 h 30 25 Qv 1 5 Qv 4 Qv 3 Qv 2 15 Plage d utilisation volet RRKZ RRKZ airflow adjustment range KDTR F400 RRKZ Pstat Pa 15 12...

Page 10: ...he transmission of vibrations Leave a minimum distance L of 60cm on the transmission side for any technical work to be performed Do not obstruct the ventilation slits on either side of the unit 3 5 2...

Page 11: ...el Do not forget the earthing connection In addition the cables routing must be protected from mechanical aggressions when the connection is made to the motor s terminal box or to the unit s safety sw...

Page 12: ...rs check the direction of rotation of the fan for the two speeds Three phase motors U1 V1 W1 V2 U2 W2 Moteur D230 Y400V Moteur 1V Alim tri 230Vac 50Hz PE L2 L3 L1 0 GV U1 V1 W1 V2 U2 W2 Moteur D230 Y4...

Page 13: ...In order to start up the fan make sure that the whole unit including fan motor and transmission rotates freely and that there is no object that may be projected by the fan The unit must be connected...

Page 14: ...en the lugs if necessary Pressure switch Check the electrical aeraulic connections Check the operation Control box Make sure that there are no defects check the connections in particular the ground co...

Page 15: ...re that they press against the bottom of the 2 grooves so that the threading of the pulley is not damaged To reduce the rotation speed loosen the mobile flange To increase the rotation speed tighten t...

Page 16: ...constant bid to improve equipment the manufacturer reserves the right to undertake any technical alteration without any notice VIM Les pr s de M gy Sud SOUDAN CS 60120 79401 ST MAIXENT L ECOLE CEDEX T...

Reviews: