background image

9

Installing the Fireplace

Step 1.

Locating the Fireplace

For space and clearance requirements for locating a fire-
place within a room see Figure 2.

A

B

C

D

E

42”

22”

36”

51”

72”

For minimum clearances, see the direct vent termination
clearance diagrams on pages 24 and 25 in this manual.

Minimum Clearances

 from the Vent Pipe to Combustible Materials

Inches

mm

Vertical Sections

. .............. 1................. 25

Horizontal Sections

Top ...................................... 3................. 75
Bottom ................................ 1................. 25
Sides .................................. 1................. 25

At Wall Firestops

Top ................................... 2 1/2 ............. 63.7
Bottom .............................. 1/2 ............... 13
Sides .................................. 1................. 25

E

1/2“ MIN. (13mm)

D

B

A

C

1” MIN. (25mm)

Clearance Requirements

The top, back, and sides of the fireplace are defined by
stand-offs. The minimum clearance to a perpendicular wall
extending past the face of the fireplace is one inch (25 mm).
The back of the fireplace may be recessed 21 1/2 inches
(546 mm) into combustible construction.

NOTE

: The distance from the unit to combustible con-

struction is to be measured from the unit outer wrap
surface to the combustible construction,

NOT

 from the

screw heads that secure the unit together.

Constructing the Fireplace Chase

A chase is a vertical box-like structure built to enclose the
gas fireplace and/or its vent system. Vertical vents that run
on the outside of a building may be, but are not required to
be, installed inside a chase.

CAUTION: TREATMENT OF FIRESTOP SPACERS AND
CONSTRUCTION OF THE CHASE MAY VARY WITH THE
TYPE OF BUILDING. THESE INSTRUCTIONS ARE NOT
SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL
BUILDING CODES. THEREFORE, YOUR LOCAL BUILD-
ING CODES MUST BE CHECKED TO DETERMINE THE
REQUIREMENTS FOR THESE STEPS.

Factory-built fireplace chases should be constructed  in the
manner of all outside walls of the home to prevent cold air
drafting problems. The chase should not break the outside
building envelope in any manner.

This means that the walls, ceiling, base plate and cantilever
floor of the chase should be insulated. Vapor and air infiltra-
tion barriers should be installed in the chase as per regional
codes for the rest of the home. Additionally, we recommend
that the inside surfaces be sheetrocked and taped for maxi-
mum air tightness.

To further prevent drafts, the firestops should be caulked to
seal gaps. Gas line holes and other openings should be
caulked or stuffed with insulation. If the unit is being in-
stalled on a cement slab, we recommend that a layer of
plywood be placed underneath to prevent conducting cold
up into the room. Be sure to include spark arrestors for
woodburning units if they are required.

THE CHASE SHOULD BE CONSTRUCTED SO THAT ALL
CLEARANCES TO THE FIREPLACE ARE MAINTAINED
AS SPECIFIED WITHIN THIS INSTALLERS GUIDE.

   Figure 2.    Fireplace Dimensions, Locations,
                     and Space Requirements

Minimum Clearances

 from the Fireplace to Combustible Materials

Inches

mm

Glass Front ........................ 36 ..................... 914

Floor .................................... 0 ........................ 0
Rear ................................... 1/2 ..................... 13
Sides ................................. 1/2 ..................... 13

Surround Sides* .................. 0 ........................ 0
Top .................................... 3 1/2 .................... 89
Ceiling** .............................. 31 ..................... 787

*  See Figure 3
** The clearance to the ceiling is measured from the top

of the unit, excluding the standoffs (see Figure 37).

Summary of Contents for QV36D

Page 1: ...CE FOR FUTURE REFERENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home wherenotprohibited by local codes 2 This appliance is only for use with the ty...

Page 2: ...instructions may result in a possible fire hazard and will void the warranty Prior to the first firing of the fireplace READ the Using Your Fireplace section of the Owners Guide DO NOT USE this applia...

Page 3: ...9 C Vent Termination 23 Step 4 Positioning Leveling and Securing the Fireplace 26 Step 5 The Gas Control Systems 26 Step 6 The Gas Supply Line 27 Step 7 Gas Pressure Requirements 27 Step 8 Wiring the...

Page 4: ...odes or in the absence of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSA C22 1 Canadian Electric Code in Canada This model may be installed in a bedroom...

Page 5: ...will void the own er s warranty and may present a fire hazard Getting Started The Hearth Home Technologies Warranty will be voided by and Hearth Home Technologies disclaims any responsibility for the...

Page 6: ...5 8 219mm VENT COLLARS ELECTRICAL ACCESS 26 7 8 682mm 12 3 4 323mm 3 1 2 90mm GAS LINE ACCESS 2 1 8 55mm 6 7 8 174mm 14 1 4 362mm 8 5 8 219mm VENT COLLARS 21 1 2 548mm 11 5 8 297mm 28 1 2 724mm TOP S...

Page 7: ...TRUCTIONS ARE NOT SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL BUILDING CODES THEREFORE YOUR LOCAL BUILD ING CODES MUST BE CHECKED TO DETERMINE THE REQUIREMENTS FOR THESE STEPS Factory built fireplace ch...

Page 8: ...ION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING 1 2 CLEARANCE FROM BACK OF FIREPLACE TO COMBUSTIBLE 0 CLEARANCE TO FRAMING MEMBER 0 CLEARANCE 1 2 C...

Page 9: ...h outer pipe DV 36D 5 3 4 146mm 8 3 4 222mm 11 3 4 298mm DV 48D 7 3 8 187mm 6 5 32 156mm 11 5 8 295mm 8 5 8 220mm 8 1 2 216mm 6 7 16 164mm 11 1 16 281mm 6 1 2 165mm 8 1 2 216mm 5 1 16 129mm 8 5 8 220m...

Page 10: ...g configuration used Terminations Kits HORIZONTAL TERMINATION WALL FIRESTOP 90 DEGREE ELBOW VERTICAL TERMINATION STORM COLLAR ROOF FLASHING HORIZONTAL PIPE SUPPORT PIPE LENGTH WALL BRACKET CEILING FIR...

Page 11: ...the four screws securing it in place see Figure 7 Figure 8 Flue Restrictor BREAK HERE Figure 7 EXHAUST SHIELD FLUE RESTRICTOR 2 Break the Flue Restrictor into two pieces Do this by bending the part b...

Page 12: ...3 Match the amount of vertical you have in the sys tem with the chart to find the appropriate position to set the Flue Restrictor 1 2 3 4 5 SETTINGS 1 2 3 4 5 Figure 9 CHART Vertical Top Vent NG Top...

Page 13: ...1 MIN 305mm 2 MAX 610mm 2 MIN 610mm 4 MAX 1 22m 3 MIN 914mm 6 MAX 1 86m 4 MIN 1 22m 8 MAX 2 4m V H 40 MAX 12 4m H 8 MAX 2 4m NOTE On vertical venting configurations where the vertical component is ov...

Page 14: ...1 20 MAX 6 2m V V1 H 40 MAX 12 4m Figure 14 Venting with Two 90 Elbows VENTING WITH TWO 2 90 ELBOWS V H H H1 1 MIN 305 mm 2 MAX 610 mm 5 MAX 1 52m 2 MIN 610 mm 4 MAX 1 22 m 10 MAX 3 1m 3 MIN 914 mm 6...

Page 15: ...914mm 6 MAX 1 86m 15 MAX 4 65m 4 MIN 1 22m 8 MAX 2 48m 20 MAX 6 2m V H H1 H2 40 MAX 12 4 m H 8 MAX 2 48 m H H 1 H2 20 MAX 6 2 m V H H H1 H2 1 MIN 305mm 2 MAX 610mm 5 MAX 1 52m 2 MIN 610mm 4 MAX 1 22m...

Page 16: ...IN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m NOTE H H1 20 MAX 6 2m V V1 H H1 40 MAX 12 4m V FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m...

Page 17: ...YOU ARE NOT USING If your vertical vent component is over 10 feet you may want to install the included vertical baffle to improve flame appearance Vertical baffle is located in the bag containing the...

Page 18: ...ion with the pre ceding component attach with a minimum of two 2 sheet metal screws Figure 20 CORRECT INCORRECT 2 Fasten the shield in place using the pilot holes provided in the part The shield shoul...

Page 19: ...The center of the hole is one 1 inch 25 4mm above the center of the horizontal vent pipe Position the firestops on both sides of the hole previ ously cut and secure the firestops with nails or screws...

Page 20: ...11 inch 280mm X 280mm hole through the ceiling using the centerpoint previously marked Frame the hole with framing lumber the same size as the ceiling joists Figure 27 Ceiling Firestop Ceiling Side If...

Page 21: ...NATION CAP MUST BE POSITIONED SO THAT THE ARROW IS POINTING UP Using screws secure the cap to the exterior wall through the flanges in the cap Figure 29 Trapezoid Termination Cap WARNING THE BOTTOM OF...

Page 22: ...IS STRONGLY RECOMMENDED WHENEVER POSSIBLE TO USE THE VINYL PROTECTOR KIT 30 minimum for vinyl clad soffits a vent shall not terminate directly above a sidewalk or paved driveway which is located betw...

Page 23: ...SEE FIGURE 31 FOR MINIMUM HEIGHTS PROVIDED THE TERMINATION CAP IS AT LEAST TWO 2 FEET FROMAVERTICAL WALL AND 2 FEET BELOW AHORIZONTAL OVERHANG NOTE This also pertains to vertical vent systems in stall...

Page 24: ...o properly position level and secure the fireplace Figure 32 Proper Positioning Leveling and Securing of a Fireplace Figure 33 Gas Control System STANDING PILOT Step 5 The Gas Control System WARNING T...

Page 25: ...r and it does not penetrate the actual firebox Open the fireplace lower grille insert the gas supply line through the gas line hole and connect it to the shut off valve When attaching the pipe support...

Page 26: ...ll Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch pigtails WARNING DO NOT CONNECT 110 120 VAC TO THE WALL SWITCH OR THE CONTROL VA...

Page 27: ...TWEEN THE FINISHED WALLS AND THE FIREPLACE SURROUND TOP AND SIDES ARE SEALED A 300 F MINIMUM SEALANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE QUIRED TO BE SEALED ONLY NON COMBUSTIBLE MATERIAL US...

Page 28: ...he bag of embers provided is sufficient for 3 to 5 applications Replace the glass door and a front trim door on the unit Pull out and latch the glass clips into the groove on the glass frame Aladdin H...

Page 29: ...e control in the PILOT position turn the control knob counter clockwise to the PILOT position 6 To light the pilot press the control knob and then press the red or black piezo button once every second...

Page 30: ...selves of this air Once the purging is complete the fireplace will light and will operate normally Subsequent lightings of the fireplace will not require this purging of air from the gas supply lines...

Page 31: ...urrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a visual check of your fireplace s flame patterns Make sure the fla...

Page 32: ...he pilot and hold the valve knob in If the millivolt reading is less than 15mV replace the thermocouple b Defective valve If the thermocouple is producing more than 15 millivolts replace faulty valve...

Page 33: ...downwards lope is 1 4 inch d Glass too loose and air tight packet leaks in corners after usage Tighten the corner e Bad thermopile or thermocouple Replace if necessary f Improper vent cap installation...

Page 34: ...ssories Adjustments regular maintenance cleaning and temporary repairs do not qualify for a service call fee and will not be covered The replacement of consumer replaceable items and installation of u...

Reviews: