STANDARD RESPONSE 

ELO UPRIGHT SPRINKLER

VK530 

(STORAGE-DENSITY/AREA)

TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page.

Form No. F_010692    21.09.16     Rev 21.1

Page 4 of 5

DESIGN CRITERIA - UL

 

(Also refer to Approval Chart 1 above.)

cULus Listing Requirements:

Standard Response Extra-Large Orifice Upright Sprinkler VK530 is cULus Listed for installation in accordance with the latest edition of NFPA 13 for 

standard spray upright sprinklers:

• 

Designed for use in hazard occupancies up to and including Extra-Hazard Group II with a minimum operating pressure of 7 psi (0.5 bar).

• Sprinkler VK530 is also cULus Listed for use in High-Piled Storage Occupancies as defined in NFPA 13 with a minimum operating pressure of 7 

psi (0.5 bar). 

• 

The sprinkler installation and obstruction rules contained in NFPA 13 for standard spray upright sprinklers must be followed.

IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 

for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest 

edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and 

also with the provisions of governmental codes, ordinances, and standards, whenever applicable.

Approval Chart 1 (UL)

Standard Response Extra-Large Orifice Upright Sprinkler VK530

 

Maximum 175 PSI (12 Bar) WWP

Base Part 

Number

1

SIN

Sprinkler 

Style

Thread Size

Nominal K-Factor

Overall Length

Listings and Approvals

(Refer also to Design Criteria below.)

NPT

BSP

U.S.

metric

2

Inches

mm

cULus

4

NYC

09679

VK530

Upright

3/4”

--

11.2

161.3

2-5/16

58.7

A3, B1, C2, B4

See Footnote 6.

14819

VK530

Upright

--

20 mm

11.2

161.3

2-5/16

58.7

A3, B1, C2, B4

--

Approved Temperature Ratings

A - 286 °F (141 °C)

B - 155 °F (68 °C), 175 °F (79 °C), 200 °F 

(93 °C), and 286 °F (141 °C)

C - 155 °F (68 °C), 175 °F (79 °C), and 

200 °F (93 °C)

Approved Finishes

1 - Brass, Chrome, White Polyester

5

, Black Polyester

5

, and Black PTFE

5

2 - Wax-Coated Brass (corrosion resistant)

3 - Brass with 200 °F (93 °C) Wax Coating (corrosion resistant); Maximum ambient ceiling temperature = 150 

°F (65 °C).

4 - ENT

5

Footnotes

Base part number shown. For complete part number, refer to Viking’s current price schedule.

Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

This table shows the listings and approvals available at the time of printing. Other approvals may be in process.

Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.

cULus Listed as corrosion-resistant.

Meets New York City requirements, effective July 1, 2008.

Summary of Contents for VK530

Page 1: ...se sprinklers may be ordered and or used as open sprin klers glass bulb and pip cap assembly removed on deluge systems Refer to Ordering Instructions below 2 LISTINGS AND APPROVALS cULus Listed Category VNIV FM Approved Class 2009 Refer to Approval Chart 1 and Design Criteria on page 3 for cULus Listing requir ments and refer to Approval Chart 2 and Design Criteria on page 4 for FM Approval requir...

Page 2: ...s Refer to Table 1 Accessories Also refer to the Viking website Sprinkler Wrenches A Standard Wrench Part No 05118CW B available since 1981 Sprinkler Cabinets A Six head capacity Part No 01724A available since 1971 B Twelve head capacity Part No 01725A available since 1971 4 INSTALLATION Refer to appropriate NFPA Installation Standards 5 OPERATION During fire conditions when the temperature around...

Page 3: ...t Brown Wax 175 F 79 C Brown Wax 200 F 93 C Brown Wax 286 F 141 C Dk Brown Wax4 Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Other limits may apply depending on fire loading sprinkler location and other requirements of the Authority Having Jurisdiction Refer to specific installation standards 3 The corrosion resistant and corrosion proofing coatings h...

Page 4: ...technical data the appropriate standards of NFPA LPCB APSAD VdS or other similar organizations and also with the provisions of governmental codes ordinances and standards whenever applicable Approval Chart 1 UL Standard Response Extra Large Orifice Upright Sprinkler VK530 Maximum 175 PSI 12 Bar WWP Base Part Number1 SIN Sprinkler Style Thread Size Nominal K Factor Overall Length Listings and Appro...

Page 5: ...t the time of printing Other approvals may be in process 4 FM Approved as corrosion resistant DESIGN CRITERIA FM Also refer to Approval Chart 2 above FM Approval Requirements Standard Response Extra Large Orifice Upright Sprinkler VK530 is FM Approved as a standard response upright Non Storage sprinkler and as a standard response upright Storage sprinkler as indicated in the FM Approval Guide For ...

Page 6: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Page 7: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Page 8: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Page 9: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Page 10: ...t readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification storage height and other hazards In all cases the maximum expected ceiling temperature dictates the lowest allowable temperature classification Sprinklers located immediately adjacent to a heat sourc...

Page 11: ...ly intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity Refer to the appropriate technical data page for allowable sprinkler models temperature ratings and o...

Page 12: ...TENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 8 GUARANTEE For details of warranty refer to Viking s current list price schedule or contact Viking directly IMPORTAN...

Page 13: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...