background image

sprin klers to be tested and, if nec es -
sary, re placed af ter a spec i fied term
of ser vice. For Vi king ESFR Pen dent
Sprin klers, re fer to the In stal la tion
Stan dards (e.g., NFPA 25) and the
Au thor ities Hav ing Ju ris dic tion for the 
spec i fied pe riod of time af ter which
test ing and/or re place ment is re -
quired. Sprin klers that have op er ated
can not be re as sem bled or re used,
but must be re placed. When re plac -
ing sprin klers, use only new sprin -
klers.

C. The sprin kler dis charge pat tern is crit -

i cal for proper fire pro tec tion. There -
fore, noth ing should be hung from, at -
tached to, or oth er wise ob struct the
dis charge pat tern. All ob struc tions
must be im me di ately re moved or, if

nec es sary, ad di tional sprin klers in -
stalled.

D. When re plac ing ex ist ing sprin klers,

the sys tem must be re moved from
ser vice. Re fer to the ap pro pri ate sys -
tem de scrip tion and/or valve in struc -
tions. Prior to re mov ing the sys tem
from ser vice, no tify all Au thor ities
Hav ing Ju ris dic tion. Con sid er ation
should be given to em ploy ment of a
fire pa trol in the af fected area.

1. Re move the sys tem from ser vice,

drain all wa ter, and re lieve all pres -
sure on the pip ing.

2. Using the spe cial sprin kler wrench,

re move the old sprin kler and in stall 
the new unit. Care must be taken
to en sure that the re place ment
sprin kler is the proper model and
style, with the cor rect or i fice size,

tem per a ture rat ing, and re sponse
char ac ter is tics. A fully stocked
spare sprin kler cab i net should be
pro vided for this pur pose.

3. Place the sys tem back in ser vice

and se cure all valves. Check the
re placed sprin klers and re pair all
leaks.

E. Sprin kler sys tems that have been

sub ject to a fire must be re turned to
ser vice as soon as pos si ble. The en -
tire sys tem must be in spected for
dam age and re paired or re placed as  
nec es sary. Sprin klers that have been 
ex posed to cor ro sive prod ucts of
com bus tion, but have not op er ated,
should be re placed. Re fer to the Au -
thor ities Hav ing Ju ris dic tion for min i -
mum re place ment re quire ments.

Form No. F_060198

Sprin kler 120 d

 

TECH NI CAL DATA

ESFR PEN DENT SPRIN KLERS

SIN VK500 (K = 14.0)

De cem ber 10, 2004

Re places sprin kler page 120 a-d, dated Feb ru ary 20, 2004
(referenced NFPA 13 ex cep tions to ESFR sprin kler spac ing rules).

Summary of Contents for SIN VK500

Page 1: ... specified materials up to 35 ft 10 7 m high in buildings with 40 ft 12 2 m high ceilings with no in rack sprin klers TECHNICAL DATA ESFR PENDENT SPRINKLERS SIN VK500 K 14 0 Sprinkler Temp Classification Nominal Temperature Rating Fusing Point 2 Maximum Ambient Ceiling Temperature1 Frame Paint Color Ordinary 165 F 74 C 100 F 38 C None Intermediate10 205 F 96 C 150 F 65 C White Approval Chart Vikin...

Page 2: ...ation Maximum Roof or Ceiling Slope 2 in 12 167 mm m or 9 5 degrees Note If the ceiling is beam and girder or panel construction locate sprinklers in the bays rather than under the beams Sprinkler Position Approved for use only in the pendent position in wet systems FM Global Loss Prevention Data Sheet 2 2 provides the following positioning require ment Install K14 0 ESFR sprinklers with the cente...

Page 3: ...build up of compound in the sprinkler orifice E With the sprinkler contained in the plastic protective cap install the sprinkler onto the piping by apply ing the special sprinkler wrench shown in Figure 1 to the sprinkler wrench flats only while taking care not to damage the sprinkler operating parts DO NOT use any other type of wrench as this could damage the unit DO NOT use the sprinkler deflect...

Page 4: ... of a fire patrol in the affected area 1 Remove the system from service drain all water and relieve all pres sure on the piping 2 Using the special sprinkler wrench remove the old sprinkler and install the new unit Care must be taken to ensure that the replacement sprinkler is the proper model and style with the correct orifice size temperature rating and response characteristics A fully stocked s...

Reviews: