MICROMATIC

®

 STANDARD 

RESPONSE UPRIGHT 

SPRINKLER VK100 (K5.6)

TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Page 3 of 6

Form No. F_052014  Rev 14.1

TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES

Sprinkler Temperature 

Classification

Sprinkler Nominal 

Temperature Rating

1

Maximum Ambient 

Ceiling Temperature

2

Bulb Color

Ordinary

135 °F (57 °C)

100 °F (38 °C)

Orange

Ordinary

155 °F (68 °C)

100 °F (38 °C)

Red

Intermediate

175 °F (79 °C)

150 °F (65 °C)

Yellow

Intermediate

200 °F (93 °C)

150 °F (65 °C)

Green

High

286 °F (141 °C)

225 °F (107 °C)

Blue

Extra High

360 °F (182 °C)

300 °F (149 °C)

Mauve

Ultra High

3

500 °F (260 °C)

465 °F (240 °C)

Black

Sprinkler Finishes:

 Brass, Chrome, White Polyester, Black Polyester, and ENT

Corrosion-Resistant Coatings

4

:

 White Polyester, Black Polyester, and Black PTFE in all temperature ratings. ENT in all temperature 

ratings except 135 °F (57 °C).  Wax-Coated Brass and Wax over Polyester

5

 for sprinklers with the following temperature ratings:

  135 °F (57 °C) Off-White Wax          155 °F (68 °C) Lt. Brown Wax       175 °F (79 °C) Brown Wax      200 °F (93 °C) Brown Wax      

286 °F (141 °C) Dk. Brown Wax

5

 

Footnotes

1

 The sprinkler temperature rating is stamped on the deflector. 

2

 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. 

Refer to specific installation standards.

3

 Sprinklers of Ultra-High temperature rating are intended for use inside ovens, dryers, or similar  enclosures with normal operating temperatures above 

300 °F (149 °C). Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 °F (149 °C), 

response time may be severely retarded.

4

 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These 

tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are com-

patible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces 

only. Note that the spring is exposed on sprinklers with Polyester and ENT coatings. For ENT coated automatic sprinklers, the waterway is coated. 

5

 Wax melting point is 170 °F (76 °C) for 286 °F (141 °C) temperature rated sprinklers.

Figure 1:  

Standard Sprinkler Wrench 10896W/B

Protective Sprinkler Cap

Wrench Flat

Summary of Contents for Micromatic VK100

Page 1: ...bar wwp Factory tested hydrostatically to 500 psi 34 5 bar Thread size 1 2 NPT 15 mm BSP Nominal K Factor 5 6 U S 80 6 metric Glass bulb fluid temperature rated to 65 F 55 C Overall Length 2 3 8 60 mm cULus Listing FM Approval and NFPA 13 installs require a minimum of 7 psi 0 5 bar The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi 0 35 bar Metric K factor measurement shown is ...

Page 2: ...1 B Twelve head capacity Part No 01725A available since 1971 4 INSTALLATION Refer to appropriate NFPA Installation Standards 5 OPERATION During fire conditions the heat sensitive liquid in the glass bulb expands causing the glass to shatter releasing the pip cap and sealing spring assembly Water flowing through the sprinkler orifice strikes the sprinkler deflector forming a uniform spray pattern t...

Page 3: ...86 F 141 C Dk Brown Wax5 Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Other limits may apply depending on fire loading sprinkler location and other requirements of the Authority Having Jurisdiction Refer to specific installation standards 3 Sprinklers of Ultra High temperature rating are intended for use inside ovens dryers or similar enclosures with ...

Page 4: ...r shown by 10 0 3 This table shows the listings and approvals available at the time of printing Check with the manufacturer for any additional approvals 4 Listed by Underwriters Laboratories Inc for use in the U S and Canada 5 cULus Listed as corrosion resistant 6 Other colors are available on request with the same Listings and Approvals as the standard colors 7 Sprinklers of Ultra High temperatur...

Page 5: ...is table shows the listings and approvals available at the time of printing Check with the manufacturer for any additional approvals 4 Other colors are available on request with the same Approvals as the standard colors 5 Sprinklers of Ultra High temperature rating are intended for use inside ovens dryers or similar enclosures with normal operating temperatures above 300 F 149 C Where the ambient ...

Page 6: ...No F_052014 Rev 14 1 Figure 2 Wrench 13577W B for Wax Coated Sprinklers Wax Coated Upright Sprinkler Step 1 Carefully slide the wrench sideways around the deflector ensuring engage ment with the sprinklger wrench flats Sprinkler wrench 13577W B must be used for installing wax coated sprinklers A 1 2 ratchet is required not available from Viking Step 2 Carefully press the wrench downward and ensure...

Reviews: