background image

1. PRO DUCT NAME

Vi king Ho ri zon

®

 Mi rage

®

 Quick Re -

sponse Ex tended Cov er age Con cealed
Pen dent Sprin klers

Model B-1 Stan dard Or i fice Sprin -
kler Base Part No. 08498
     Avail able since 1993

Model B-2 Large Or i fice Sprin klers:
A. Base Part No. 10485
     Avail able since 1998
B. Base Part No. 10680
    Avail able since 1999

Cover Plate As sem bly Part No. 09804
Avail able since 1996

2. MAN U FAC TURER

The Vi king Cor po ra tion
210 N. In dus trial Park Road
Hastings, Mich i gan 49058 U.S.A.
Tele phone:

(616) 945-9501
(877) 384-5464

Fax:

(616) 945-9599

e-mail: [email protected]

3. PRO DUCT DE SCRIP TION

Vi king Ho ri zon

®

 Mi rage

®

 Quick Re -

sponse Ex tended Cov er age Con cealed
Pen dent Sprin klers are small, sol der link 
and le ver spray sprin klers de signed for
in stal la tion on con cealed pipe sys tems.
Equipped with a spe cial de flec tor, the
sprin kler is de signed to meet Light-Haz -
ard den sity re quire ments for spe cific ex -
tended ar eas of cov er age when the re -
quired min i mum wa ter sup ply is pro -
vided at the sprin kler.
Af ter the sprin kler sys tem has been
tested and the ceil ing fin ish ap plied, the
sprin kler is hid den from view by a low-
pro file, small di am e ter cover plate, in -
stalled flush to the ceil ing. The cover
plate is avail able in sev eral dec o ra tive
fin ishes to meet de sign re quire ments.
The “push-on”, “thread-off” de sign al lows
for easy in stal la tion of the cover plate, with 
up to 1/2" (12,7 mm) of ver ti cal ad just -
ment. The “thread-off” fea ture is de signed
to pre vent un wanted dis en gage ment of
the cover as sem bly. The cover as sem bly
can be re moved and re in stalled to per mit
tem po rary re moval of ceil ing pan els with -
out tak ing the sprin kler sys tem out of ser -
vice and re mov ing the sprin kler.
In side the body of the Ho ri zon

®

 Mi rage

®

Quick Re sponse Ex tended Cov er age
Con cealed Sprin kler, the de flec tor and
seal ing as sem bly are held in po si tion by
a fast-acting heat-sensitive fus ible link.
The sprin klers are listed as quick re -
sponse sprin klers when in stalled ac -
cord ing to the listed 16 ft. x 16 ft. (4,9 m x
4,9 m) or 18 ft. x 18 ft. (5,5 m x 5,5 m)

spac ing. (Re fer to the ap proval chart on
page 58 d for ad di tional list ing.) 
Dur ing fire con di tions, when the tem per -
a ture around the sprin kler ap proaches
its op er at ing tem per a ture, the cover
plate de taches. Con tinued heat ing of
the ex posed sprin kler causes the fus ible 
link to dis en gage, re leas ing the de flec -
tor and seal ing as sem bly. Wa ter flow ing
through the sprin kler or i fice strikes the
de flec tor, form ing a uni form spray pat -
tern to ex tin guish or con trol the fire.

4. TECH NI CAL DATA

LIST INGS:  UL Listed, Guide No. VNIV for

Light-Hazard occupancies with
smooth, flat, hor i zon tal ceil ings only.
Re fer to Ta ble 1 on page 58 d.

Rated to 175 psi (1 207 kPa) wa ter work ing 

pres sure.

Fac tory tested pneu mat i cally to 95 psi

(655 kPa).

Spring: U.S.A. Pat ent No. 4,570,720

Thread Sizes:

Part Nos. 08498 and 10485: 1/2" (15

mm) NPT

Part No. 10680: 3/4" (20 mm) NPT

Or i fice Sizes:

Part No. 08498: Stan dard Orifice
Part Nos. 10485 and 10680: Large

Orifice

K-factors:

Part No. 08498: Nom i nal 5.5 U.S.

(7,9 met ric*)

Part Nos.10485 and 10680: Nominal

8.0 U.S. (11,5 met ric*)

*  Met ric K-factor shown is for use when  pres sure

is mea sured in kPa. When pressure is mea -
sured in BAR, mul ti ply the  met ric K-factor
shown by 10.0.

Min i mum op er at ing pres sure: 7 psi (48,3

kPa)

Max i mum dis tance from sprin klers to
walls: One-half the sprin kler spac ing in di -
cated in Ta ble 1 for the “Min i mum Wa ter
Sup ply Re quire ment” used. 

Available Cover Plate Ver ti cal Ad just ment:

1/2" (12,7 mm) +/- 1/4" (6,4 mm)

SPRIN KLER MA TE RIALS
Body: Brass Cast ing UNS-C84400
Body Cap: Brass UNS-C26000
De flec tor: Cop per UNS-C19500

De flec tor Pins: Stain less Steel UNS-

S30300

Le ver Bar: Cop per Al loy UNS-C72500

Com pres sion Screw: Brass UNS- C36000
Fus ible Link As sem bly**: Nickel Al loy and

Eutectic Sol der

**Fus ible links of Ho ri zon

®

  Mi rage

®

 Quick Re -

sponse  Ex tended Cover age  Con cealed Pen -
dent Sprin klers are  marked with a yel low stripe
or dot for  iden ti fi ca tion pur poses only.

Fus ible Link Le vers: Stain less Steel

UNS-S31600

Seal: Tef lon

®

 Tape

Spring: Nickel Al loy
COVER PLATE AS SEM BLY MA TE -
RIALS 

Cover Plate As sem bly: Brass UNS-

C26000

Spring: Nickel Al loy
Sol der: Eutectic

COVER FIN ISHES

Bright Brass
Pol ished Chrome
Painted

1

 White (No. 1004

2

Painted

1

 Ivory (No. 1634

2

)

Painted

1

 Black (No. 1007

2

)

1

 Painted fin ish con sists of Poly es ter Baked

Enamel.

2

 Sherwin-Williams

®

  Color An swers™ Interior

Color Num ber. Other col ors are  avail able on re -
quest. See  Sherwin-Williams

®

 Color An -

swers™ Interior Color Se lec tion color num bers.

OR DERING IN STRUC TIONS
Ho ri zon

®

 Mi rage

®

 Sprin klers and cover

plates must be or dered sep a rately.
To or der the Ho ri zon

®

 Mi rage

®

 Quick

Re sponse Ex tended Cov er age  Con -
cealed Pen dent Sprin kler, re fer to:

1. Model B-1 Stan dard Or i fice Sprin kler

Base Part No. 08498  or

2. Model B-2 Large Or i fice Sprin kler:

May 25, 2000

Sprin kler 58 a

Form No. F_050493

Note: Units of mea sure in pa ren the ses  may  be ap prox i ma tions.

Re places page 58 a-d, dated Oc to ber 20, 1999. (These
sprin klers are avail able with 220 °F tem per a ture rat ing).

Cover Plate As sem bly: P/N 09804

1/2" NPT Sprin klers:

P/N 08498 (std. or i fice)

P/N 10485 (large or i fice) 

3/4" NPT Sprin kler:

P/N 10680

(large or i fice)

For Light Haz ard Oc cu pancies Only

TECH NI CAL DATA

 

HO RI ZON

®

 

 MI RAGE

®

QUICK RE SPONSE

EX TENDED COV ER AGE

CON CEALED SPRIN KLERS

Ho ri zon

®

 Mi rage

®

 Con cealed Sprin kler

In stalled in Acous ti cal Ceil ing

OBSOLETE

Summary of Contents for HORIZON MIRAGE

Page 1: ...t Hazard occupancies with smooth flat horizontal ceilings only Refer to Table 1 on page 58 d Rated to 175 psi 1 207 kPa water working pressure Factory tested pneumatically to 95 psi 655 kPa Spring U S A Patent No 4 570 720 Thread Sizes Part Nos 08498 and 10485 1 2 15 mm NPT Part No 10680 3 4 20 mm NPT Orifice Sizes Part No 08498 Standard Orifice Part Nos 10485 and 10680 Large Orifice K factors Par...

Page 2: ...nklers should be destroyed immedi ately C Horizon Mirage Quick Response Concealed Sprinklers must be installed in neutral or negative pressure ple nums only D Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be ex posed to temperatures that exceed the maximum recommended ambient tem peratureforthetemperature ratingused E Horizon Mira...

Page 3: ...ted or me chanically damaged must be replaced immediately Sprinklers showing signs of corrosion shall be tested and or re placed immediately as required Instal lation standards require sprinklers to be tested and if necessary replaced immediately after a specified term of service Refer to the installation stan dards and the Authority Having Juris diction for the specified period of time after whic...

Page 4: ...s Sprinkler Part Numbers3 NPT Thread Size Maximum Areas of Coverage5 Nominal K Factor Minimum Water Supply Requirements5 Listings4 Length x Width UL7 C UL7 NYC Inches mm U S metric6 10485 1 2 15 16 ft x 16 ft 4 9 m x 4 9 m 8 0 11 5 26 gpm 10 6 psi 98 4 L min 75 kPa A1 A1 10680 3 4 20 10485 1 2 15 18 ft x 18 ft 5 5 m x 5 5 m 8 0 11 5 33 gpm 17 0 psi 124 9 L min 118 kPa A1 A1 10680 3 4 20 10485 1 2 ...