FREEDOM
®
RESIDENTIAL
CONCEALED HORIZONTAL
SIDEWALL SPRINKLER VK490
(K5.9)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page.
Form No. F_032116 Rev 01 September 7, 2022
Page 2 of 7
Cover Plate Assembly:
Base Part No. 16207 (3-5/16” diameter)
Specify finish and temperature rating of the cover plate assembly by adding
the appropriate suffixes for the finish and the cover temperature rating to
the base part number:
Finish Suffixes: White Polyester = M-/W, Chrome = F
Temperature Suffix: 139 °F (59 °C) = A, 165 °F (74 °C) = C
For example, cover 16207 with a White Painted finish and a 139 °F (59 °C)
temperature rating = 16207MA/W.
Available Finishes And Temperature Ratings:
Refer to Table 1.
Accessories:
(Also refer to the Viking website.)
Sprinkler Wrenches**:
A. Heavy Duty Wrench Part No. 16208W/R** (available since 2010)
B. Head Cabinet Wrench Part Number 16267
***
(available since 2010)
C. Optional Cover Plate Installer Tool Part No. 14867 (available since 2007)
**Requires a ½” ratchet (not available from Viking).
***Ideal for sprinkler cabinets.
Sprinkler Cabinet:
Part No. 01731A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, when the temperature around the sprinkler approaches
its operating temperature, the cover plate detaches. Continued heating of the
exposed sprinkler causes the fusible element to disengage, releasing the sealing assembly. Water flowing through the sprinkler
orifice strikes the flow shaper, forming a uniform spray pattern over a specific area of coverage determined by the water supply
pressure at the sprinkler to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Freedom
®
Residential Concealed Horizontal Sidewall Sprinkler VK490 is available through a network of domestic and
international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature
Classification
Sprinkler Nominal
Temperature Rating
1
Maximum Ambient
Ceiling Temperature
2
Temperature Rating of the
Cover Assembly (Required)
Cover Plate
Base Part Number
3
Ordinary
165 °F (74 °C)
100 °F (38 °C)
139 °F (59 °C)
16207
Intermediate
205 °F (96 °C)
150 °F (65 °C)
165 °F (74 °C)
16207
Sprinkler Finishes:
Brass
Cover Plate Finish:
White Polyester, Chrome
Footnotes
1.
The sprinkler temperature rating is stamped on the inlet.
2.
Based on NFPA-13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the
Authority Having Jurisdiction. Refer to specific installation standards.
3.
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
Figure 1: Identification of Custom Paint for
Concealed Covers
All custom color painted cover plates will have an
identifying label affixed to the inside of the cover
that indicates the custom color and will have a
representative sample (a paint dot) of the paint
on the label.
FA
C
TO
R
Y
A
PP
LIE
D CUSTOM
PA
IN
T C
O
LO
R