background image

49 

7.   With the CS-1’s switch in the “OFF” position turn on the power supply to the 

unit. Turn the “Off-On” switch to “ON”. 

8.  Switch the “Man-O-AUTO” switch on the unit control panel to “Man”. Liquid 

will begin to fill the selected system. 

9.   As the system fills, monitor the system vent/bleed valves. Close each valve 

when liquid leaks from it. 

10.  When the liquid leaks from the uppermost vent/bleed valve, close the vent 

valve. The system pressure switch will close that system’s solenoid valve. 
The pump pressure switch will turn the pump off. 

11.  If another system is to be filled, turn the “Man-O-AUTO” switch to OFF and 

select the next system using switches A and B. 

12.   Turn the “Man-O-AUTO” switch to “Man” and repeat steps 8 through 10. 
13.  After filling all systems and the CS-1 tank, close the supply isolation valve. 
14.  All air must be out of the system before switching the unit to maintenance 

mode. Follow the system manufacturer’s recommendations to ensure all air 
is removed. 

 
 

16.0  SYSTEM AND SOLUTION TEST AND MAINTENANCE 

 

Field mixing of propylene glycol and site water is strictly prohibited, as the control of the 
mixture cannot be assured. Improper field mixing of solution can result in reduced 
capability to prevent freezing or to control a fire. Firefighter Eliminator F is already 
premixed and ready to use. 
 

Filling the System 

In the main drain line between the valve and primary check valve inlet, a tee is provided 
with a 1” NPT connection for supply and maintenance of the antifreeze solution to the 
system above the check valve. A suitable portable pump can be utilized to fill the system 
to the static water pressure. (The CS-1 pump can be used for filling the system initially at 
15 GPM (56 l/min) to 100 ft. head pressure or system static pressure. However, it is a 
less efficient pump for filling the system because of the duration of time required to do 
so. The CS-1 pump is to be utilized to bring the solution to maintenance pressure 
[recommended 50 PSI (344 kPa)] and is designed to maintain supervisory pressure 
once the system is initially filled. When filling the system with antifreeze solution, all air 
must be bled from the system (as described in data page 45 a-j) in order to make final 
and maintained antifreeze solution pressure non-compressible. 
 

16.1 

Testing the Solution 

 

Antifreeze solution shall be checked quarterly (for gridded systems), or semi-
annually (for tree type configurations) with a refractometer to detect the 
concentration of antifreeze solution and effectiveness against freezing. Sampling 
shall be taken from multiple points within the freezer system (refer to the 
instructions on data pages 45 e and 45 i for fluid sampling). When draining 
sample antifreeze solution from the system, be sure to shut off the system control 
valve directly upstream of the deluge valve so that water doesn’t enter the 
system. After the CS-1 pump has restored the antifreeze solution pressure, 
ensure that the water supply control valve is returned to the fully open position 
once fluid sampling is completed. Multiple propylene glycol/water solution test 

Summary of Contents for ESFR

Page 1: ...INGLE INTERLOCKED PREACTION COLD STORAGE SYSTEM MANUAL The Viking Corporation 210 N Industrial Park Road Hastings MI 49058 Telephone 269 945 9501 Technical Services 877 384 5464 Fax 269 945 9599 Decem...

Page 2: ...14 5 1 1 1 General Piping and Material Recommendation 15 5 1 2 Primary Check Valve Main Drain 16 5 1 3 Reclaim Tank 17 5 1 4 Automatic Pressure Control System 17 5 1 5 Solution Test Valves 18 5 1 6 R...

Page 3: ...36 7 4 2 Handling 36 7 4 3 Location 36 7 4 4 Piping and Connections 36 7 5 Electrical Connections 37 7 6 Start up 38 8 0 Pressure Switch 38 8 1 System Control Switch 38 8 2 Wiring Diagram 39 8 3 Press...

Page 4: ...Fill Procedure 47 15 1 Filling the Reservoir Tank 47 15 1 1 Gravity Fill 47 15 1 2 Pump Assist Fill 47 15 2 Filling Systems 48 16 0 System Solution Test and Maintenance 49 16 1 Testing the Solution 4...

Page 5: ...5 Figure 1 Straight Through Configuration...

Page 6: ...6 Figure 2 Angle Style Configuration...

Page 7: ...ssure Upon operation of the sprinkler s the pressurized propylene glycol water solution is distributed from the sprinkler Water from the supply system pushes out the propylene glycol water solution at...

Page 8: ...m run of pipe For systems in unheated areas subject to freezing branch lines shall be pitched at per 10 ft 4 mm m and mains at per 10 ft 2 mm m run of pipe This system shall be designed by qualified f...

Page 9: ...m with ceiling height up to 45 ft 3 in 13 8 m with a minimum system design pressure of 60 PSI 414 kPa 3 0 SYSTEM DESIGN 3 1 Hydraulic Calculations At 21 F 29 4 C the 50 solution of propylene glycol w...

Page 10: ...10...

Page 11: ...ata and a listed Viking single interlocked preaction assembly two Viking Easy RiserTM Check Valves The first or primary Easy RiserTM Check Valve and trim includes connections for antifreeze supply fro...

Page 12: ...antifreeze from the freezer and protect the primary check valve from freezing near the atmospheric air surface of the clapper and seat This valve includes a main drain and a special 3 8 I D copper tub...

Page 13: ...nts apply to installation of the Viking ESFR Cold Storage System with the following exceptions Commodity limited to Class II or less limited to wood pallets Maximum ceiling height to bottom of inside...

Page 14: ...ncluding test pressures of pumps at zero flow Detection System shall be capable of operation prior to or equal to an ESFR Sprinkler having an RTI Response Time Index of 50 or less No linear detection...

Page 15: ...ater solution in the system Additional vent or bleed valves shall be installed on the end of each branch line at high points and feed mains at high points to ensure air is vented from the system This...

Page 16: ...e glycol solution A re claim tank with adequate capacity of the largest system s shall be located near the system riser s System drain piping shall be arranged to discharge to the re claim tank 5 1 2...

Page 17: ...of the largest system volume installed The tank shall be utilized as a reclaim tank for the propylene glycol solution in the system piping when the system s are drained for system service and for dis...

Page 18: ...ary Easy RiserTM check valve The most remote location from the Easy RiserTM check valve One valve located at the end of 50 of the line piping directly on the Model AV 1 Air Vent Valve assembly A test...

Page 19: ...ation of the system might occur due to temperature fluctuation is in a warm up mode of the freezer which is very rare once it is put into service Also variation in system pressure due to temperature d...

Page 20: ...backup power system to the freezer temperature control system If the pressure should increase due to warm up above the rated static pressure of the system the pressure relief valve or automatic contr...

Page 21: ...jacent to the system inlet that monitors the antifreeze solution pressure and signals the CS 1 pump to maintain pressure in the proper range The CS 1 pump provides a 5 GPM 18 9 l min flow at a minimum...

Page 22: ...that is certified by the manufacturer or a third party agency is to be installed in the system piping Field mixing of propylene glycol and site water is strictly prohibited as the control of the mixtu...

Page 23: ...m side is required in order to provide a low pressure alarm in the case of antifreeze pressure loss due to sprinkler operation without a fire condition In this case the antifreeze supply must be manua...

Page 24: ...nance solution supply tank The CS 1 pump will stop running when the pressure in the section of piping is 50 PSI 344 kPa minimum or the set pressure of the system pressure switch Ensure there is no tra...

Page 25: ...fill pump NOT the CS 1 pump to the connection located on the main drain assembly 3 Close the main drain valve vent bleed valves and low point drains if opened Ensure there are no openings on system p...

Page 26: ...to close at a pressure below the PRV set point and open above the shut off pressure of the sprinkler system control switch of the pump system A normally closed solenoid valve is to be installed on the...

Page 27: ...supply required is 115 volt 50 or 60 hz with 15 20 amp GFI protected circuit The solenoid valve is wired directly through the system pressure switch and system alarm pressure switch as described belo...

Page 28: ...previously set value Depress the Set button and hold until the value changes 5 seconds Set the value to 0 10 Depress the Mode Enter button to return to dr1 11 Depress the Mode Enter button several ti...

Page 29: ...r should only be used if there is a value in COF 6 5 DAP should always be set at 0 to ensure that the system shuts down the solenoid as soon as the pressure is obtained DiS should be set at d1 d2 or d...

Page 30: ...uipment is designed to be safe in the use for which it was planned provided it is installed started up operated and maintained in accordance with the instructions in this manual Therefore all personne...

Page 31: ...the fill process The CS 1 pump is to be utilized to bring the solution to maintenance pressure normally 50 PSI 344 kPa pressure at the primary check valve and is designed to maintain system pressure...

Page 32: ...the pump will turn on until the pressure at the CS 1 rises above a set level In Automatic mode pump operation is inhibited if the level of liquid in the unit s storage tank drops below the level swit...

Page 33: ...Input 5 System 1 Inputs Input 6 System 2 Inputs Input 7 System 3 Inputs Input 8 System 4 Inputs Input 9 System 5 Inputs Input 10 System 6 Inputs Input 11 Switch A Down Position Input 12 Switch A Up Po...

Page 34: ...tput 8 SYSTEM 6 SOLENOID VALVE Output 8 on when Manual Mode Input 1 on and Input 10 on and Input 11 on and Input 13 on OR Automatic Mode Input 2 on and Input 10 on Output 9 LEVEL SWITCH RELAY COIL Out...

Page 35: ...35...

Page 36: ...MBIENT CONDITIONS OR EXTREME DUST AND DIRT Install the CS 1 indoors in a clean dry non corrosive environment This equipment is not to be installed outdoors exposed to the weather Position the CS 1 in...

Page 37: ...red and threaded to a proper depth and length before installation Threads should be inspected for cleanliness and depth of cut Good quality pipe compound should be used to ensure a good leak tight fit...

Page 38: ...pancies before operating the unit 1 The unit is bolted to a firm level surface 2 Area temperature will always remain between 40 F and 100 F 4 and C 3 Dielectric unions if needed are installed between...

Page 39: ...parameter value Display mode the Set button is pressed until the display of the parameter value is changed Internally the unit remains in the operating mode It continues its monitoring function with...

Page 40: ...s the Mode Enter button and the value SP1 appears 17 Depress the Set button The value that appears is the factory or previously set value Depress the Set button and hold until the value changes 5 seco...

Page 41: ...t Do not over tighten a Mount the Alarm Pressure Switch in the upright position threaded connection down 3 To wire the unit proceed as follows a De energize electrical circuits involved b Use the spec...

Page 42: ...chanical properties per ISO 898 1 Class 8 8 Hex nuts and bolts are zinc electroplated followed by a yellow chromate dip Gaskets Grade E EPDM NSF 61 Certified 30 F to 230 F Service Temperature Range 40...

Page 43: ...tion during temperature cycles The lubricant on the interior of the gasket will act to improve the chemical resistance of the gasket material by providing a thin lubricant barrier between the piping s...

Page 44: ...th conventional and electric release trims The riser consists of two Viking Easy RiserTM Swing Check Valves one with special cold trim and the second with by pass trim to isolate the antifreeze in the...

Page 45: ...r use in applications having a minimum temperature as low as 8 F 13 3 C The piping system is filled with pressurized propylene glycol and water solution maintained from a pressure pump system that con...

Page 46: ...rculation allows the riser pipe to maintain a very cold temperature as supplied from the freezer area The moisture in the heated area air will cause formation of liquid on the pipe surface Due to the...

Page 47: ...pen the shut off valve on the supply container and supply isolation valve on the CS 1 5 Open the pump suction isolation valve and allow liquid to enter the reservoir tank If there is enough liquid in...

Page 48: ...p seals and possibly damage the pump impeller Follow the steps below 1 Turn off and isolate the electrical supply to the unit 2 Close the Supply Isolation and Tank Fill valves 3 If not already connect...

Page 49: ...ection for supply and maintenance of the antifreeze solution to the system above the check valve A suitable portable pump can be utilized to fill the system to the static water pressure The CS 1 pump...

Page 50: ...be drained Five percent 5 of the pendent ESFR sprinklers in all locations throughout the system are to be removed and inspected for frozen solution If any of the pendent ESFR sprinklers are found wit...

Page 51: ...1 pressure switch setting 1 Verify system pressure switch setting is correct The CS 1 pressure switch setting must not be adjusted higher Adjust CS 1 switch setting lower if approved byfactory Failure...

Page 52: ...Easy Riser Bypass Trim 14038 14039 14040 07921 Premixed Propylene Glycol Solution Firefighter Eliminator F 21 F 29 4 C 55 Gallon 208 2 liter Drum 12967 55 275 Gallon 946 3 liter Drum 12967 275 13050 1...

Page 53: ...adjusted 1 13057 Pressure Switch Cable 1 13231 Magnetic Starter 1 13058 Overload Heater Indicate Unit Voltage for Correct Selection 208V 60 HZ 3 PH 13059 230V 60 HZ 3 PH 13060 460V 60 HZ 3 PH 13061 5...

Reviews: