background image

MICROFAST

®

 QUICK 

RESPONSE FUSIBLE 

ELEMENT PENDENT 

SPRINKLER VK353 (K8.0)

TECHNICAL DATA

Page 1 of 6

Form No. F_071814   19.02.21   Rev 19.1

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

1.  DESCRIPTION

The Viking Microfast

®

 Quick Response Fusible Element Pendent Sprinkler VK353 

is a small, thermosensitive, solder link spray sprinkler available with various fin-

ishes and temperature ratings to meet design requirements. The special Polyester 

and Polytetrafluoroethelyne (PTFE) coatings can be used in decorative applica-

tions where colors are desired. 

2.  LISTINGS AND APPROVALS

cULus Listed:

 Category VNIV

FM Approved:

 Class Series 2000

Refer to Approval Chart 1 and Design Criteria cULus Listing requirements, and 

refer to Approval Chart 2 and Design Criteria for FM Approval requirements that 

must be followed.

3.  TECHNICAL DATA

Specifications:

Minimum Operating Pressure: 7 psi (0.5 bar) 

Rated to 175 psi (12 bar) water working pressure

Factory tested hydrostatically to 500 psi (34.5 bar)

Thread size: 1/2” NPT, 15 mm BSP, 3/4” NPT, 20 mm BSP

Nominal K-Factor: 8.0 U.S. (115.2 metric**)

Overall Length: 2-5/16” (59 mm)

 *cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE 

Approvals ONLY is 5 psi (0.35 bar).

Material Standards:

Frame Casting: Brass UNS-C84400 or QM Brass 

Deflector: Phosphor Bronze UNS-C51000 or Copper UNS-C19500

Fusible Element Assembly: Nickel Alloy

Trigger and Support: Stainless Steel UNS-S31600

Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape

Seat and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400

Screw: Brass UNS-C36000

For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE Coated

For Polyester Coated Sprinklers: Belleville Spring-Exposed

Ordering Information:

 (Also refer to the current Viking price list.)

Order Viking Microfast

®

 Quick Response Fusible Element Pendent Sprinkler VK353 by first adding the appropriate suffix for the 

sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. 

Finish Suffix: Brass = A, Chrome = F, White Polyester = M-W, Black Polyester = M-B, and Black PTFE = N

Temperature Suffix: 165 °F (74 °C) = C, 205 °F (96 °C) = E, and 280 °F (138 °C)

For example, sprinkler VK353 with a 3/4” NPT thread, Brass finish and a 165 °F (74 °C) temperature rating = Part No. 18274AC

Available Finishes And Temperature Ratings:

 Refer to Table 1.

Accessories:

 (Also refer to the Viking website.)

Sprinkler Wrenches:

A. Standard Wrench: Part No. 21475MB (available since 2017). 

B. Wrench for Recessed Pendent Sprinklers: Part No. 13655WB** (available since 2006)

C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool*** Part No. 15915 (available since 2010)

  **A ½” ratchet is required (not available from Viking).

     ***Allows use from the floor by attaching a length of 1” diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F_051808.

Sprinkler Cabinets:

A. Six-head capacity: Part No. 01724A (available since 1971)

B. Twelve-head capacity: Part No. 01725A (available since 1971)

Replaces Form No. F_071814 Rev 18.1.P65

(Removed F-1 Escutcheon.)

NOTE: As  of  May  2018  all  logos  have  been  removed  from 

the wrench boss.

Summary of Contents for 139676

Page 1: ...Element Assembly Nickel Alloy Trigger and Support Stainless Steel UNS S31600 Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with PTFE Tape Seat and Insert Assembly Copper UNS C1...

Page 2: ...ges releasing the seat and spring assemblies to open the waterway Water flowing through the sprinkler orifice strikes the sprinkler deflector forming a uniform spray pattern to extinguish or control t...

Page 3: ...ed not available from Viking TABLE 1 AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature...

Page 4: ...ecessed Escutcheon Footnotes 1 Base part number shown For complete part number refer to Viking s current price schedule 2 Metric K factor measurement shown is when pressure is measured in Bar When pre...

Page 5: ...ressure is measured in Bar When pressure is measured in kPa divide the metric K factor shown by 10 0 3 This table shows the FM Approvals available at the time of printing Other approvals may be in pro...

Page 6: ...Figure 4 Sprinkler Dimensions with the Model E 1 and E 2 Recessed Escutcheons Figure 3 Sprinkler Dimensions with a Standard Escutcheon 3 4 NPT 20 mm 2 5 16 59 mm 1 3 4 45 mm Installed with a standard...

Page 7: ...tall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fitti...

Page 8: ...CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkle...

Page 9: ...these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinkle...

Page 10: ...the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed...

Page 11: ...tion of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as s...

Reviews: