Viking 06932B Technical Data Manual Download Page 3

MICROFAST

®

 

QUICK RESPONSE 

PENDENT SPRINKLER 

VK3311 (K4.2)

TECHNICAL DATA

Page 3 of 5

Form No. F_061914    19.02.21    Rev 19.1

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES

Sprinkler Temperature 

Classification

Sprinkler Nominal

 

Temperature Rating

1

Maximum Ambient

 

Ceiling Temperature

2

Bulb Color

Ordinary

135 °F (57 °C)

100 °F (38 °C)

Orange

Ordinary

155 °F (68 °C)

100 °F (38 °C)

Red

Intermediate

175 °F (79 °C)

150 °F (65 °C)

Yellow

Intermediate

200 °F (93 °C)

150 °F (65 °C)

Green

High

286 °F (141 °C)

225 °F (107 °C)

Blue

Sprinkler Finishes:

 Brass, Chrome, White Polyester, Black Polyester, and Black PTFE

Corrosion-Resistant Coatings

3

:

 White Polyester, Black Polyester, and Black PTFE

Footnotes

1

 The sprinkler temperature rating is stamped on the deflector. 

2

 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. 

Refer to specific installation standards.

3

 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These 

tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compat-

ible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. 

Note that the spring is exposed on sprinklers with Polyester and PTFE coatings.

Figure 2:  

Wrench 13655W/B for Recessed Pendent Sprinklers

Carefully slide the wrench sideways around 

the protective cap, ensuring engagement with 

the sprinkler wrench flats

Sprinkler wrench 13655W/B** 

for recessed pendent 

sprinklers

** A 1/2” ratchet is required

(not available from Viking)

Summary of Contents for 06932B

Page 1: ...Casting Brass UNS C84400 Deflector Brass UNS C26000 Bushing Brass UNS C36000 Bulb Glass nominal 3 mm diameter Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with PTFE Tape Screw...

Page 2: ...s the heat sensitive liquid in the glass bulb expands causing the glass to shatter releasing the pip cap and sealing spring assembly Water flowing through the sprinkler orifice strikes the sprinkler d...

Page 3: ...Polyester and Black PTFE Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Other limits may apply depending on fire loading sprinkler location and other requi...

Page 4: ...te Polyester4 and Black Polyester4 2 Brass and Chrome Footnotes 1 Base part number shown For complete part number refer to Viking s current price schedule 2 Metric K factor measurement shown is when p...

Page 5: ...igure 4 Sprinkler Dimensions with the Model E 1 and E 2 Recessed Escutcheons Figure 3 Sprinkler Dimensions with a Standard Escutcheon 1 2 10 mm NPT 2 1 4 57 mm Installed with a standard 1 8 surface mo...

Page 6: ...tall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fitti...

Page 7: ...CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkle...

Page 8: ...these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinkle...

Page 9: ...the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed...

Page 10: ...tion of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as s...

Reviews: