background image

 

LT0186 Issue 2.80 

         27 July 2012 

Page 1 of 10 

 

T-GEN 50

 

24V Alert & Evacuate Tone Generator

 

INSTALLATION AND OPERATING INSTRUCTIONS

 

 

 
The VIGILANT  T-GEN 50 is a self-contained AS 2220 and ISO 8201 Alert and Evacuate tone generator, with speaker 
line supervision and speech. It has been designed to connect directly to fire alarm panels, but may be connected to other 
suitable digitised equipment. 
 
T-GEN 50 is available in 2 versions (see page 8 for a full list of available items and accessories): 
 
PA0766 

Tones, fault supervision and speech. Contains (SF0341) 

 Speech IC with 4 pre-recorded messages 

that are inserted into the Alert and Evacuate tones.  A microphone input is also provided for 
emergency public address and for recording messages different to the standard messages supplied.  
A suitable microphone is Part Number ME0290. 

 
PA0886 

Same as PA0766 except fitted with SF0309 software and SF0342 speech IC in which the alert 
message is a recorded bell sound.  Alert and evacuate tones may separately be disabled so only the 
recorded messages are played.  DIP switches 5-8 select different functions. 
 

Feature 

PA0766 

PA0886 

24 VDC, fault supervision, optional PA microphone 

YES 

YES 

Alert Tone  (can be separately disabled on PA0886) 

YES 

YES/Disable 

Pre-recorded Alert speech message 

YES 

BELL TONE 

Evacuation Tone AS 2220 or ISO 8201 selectable 

YES 

YES/Disable 

Pre-recorded Evacuation messages selectable 

YES 

YES 

Microphone input for emergency public address 

YES 

YES 

Custom message recording facility 

YES 

YES 

Software and speech IC fitted 

SF0308, SF0341 

SF0309, SF0342 

Switches and links used  to select different options 

YES 

YES 

Recommended for use in Schools and hospitals 

NO 

YES 

 

These instructions apply to units with V1.70 software onwards.  Refer to LT0186 Issue 2.30 for instructions for earlier 
software versions. 
 
A pre-assembled Building Occupant Warning System (BOWS) that utilises the T-GEN 50 is available in 50W and 100W 
versions (ordering codes FP1021 and FP1022). 
 

CHECKING THE KIT 

Before commencing installation, please ensure that the following items are present and undamaged: 

1 x T-GEN 50 Board 
1 x Installation & Operating Instructions (LT0186) 
1 x Background music loom  For connecting an external music source to the T-GEN MUSIC input 
1 x 6.3mm spacer   

Mounting T-GEN on earth stud 

1 x M4 washer 

 

Mounting T-GEN on earth stud 

1 x M4 nut  

 

Mounting T-GEN on earth stud 

6 x PCB standoffs     

Mounting T-GEN 

1 x 2k7 resistor         

Optional Isolate Indication 

1 x 3k3 resistor 

 

ELD for MX4428 & F3200 Ancil Relays 

2 x 10k resistor 

 

-ALM Input ELD resistor, MX4428 Ancil Relay ELD   

1 x 56k resistor 

 

100V line ELD 

2 x 100k resistor 

 

2 branch 100V line ELD 

1 x 100V Speaker Line Warning Label (LB0648) 

 

OPERATION 

Operation of T-GEN is controlled by the Auto/Isol/Evac (AIE-

) input. In the “Auto” position the Alar

m input (ALM-) is 

enabled. In the “Isol” (Isolate) position the Alarm input is disabled and any latched fault or alarm conditions are reset. In

 

the “Evac” position the Evacuate tone is generated.

 

 
In Auto mode activation of the Alarm input starts a six stage rising amplitude Alert tone. This continues until one of the 
following occurs: 

 
-  the Alarm input returns to normal (Alarm input in non-latching mode), or 
-  the AIE- input is changed to Isol, or 
-  the AIE- input is changed to Evac, or 
-  the Alert to Evacuate change-over time is reached. 

 
If the Alert to Evacuate change-over time is set to 0 sec, then no Alert tone is generated and the Evacuate tone is 
generated immediately. If the change-over time is set to Alert only, no Evacuate tone is generated and must be initiated 

Summary of Contents for T-GEN 50

Page 1: ...S These instructions apply to units with V1 70 software onwards Refer to LT0186 Issue 2 30 for instructions for earlier software versions A pre assembled Building Occupant Warning System BOWS that uti...

Page 2: ...lic address This is activated when the microphone s PTT button is pressed while the A I E switch is in the Auto or Evac position Public address overrides Alert and Evac tones A remote microphone can b...

Page 3: ...e Recorded Message OFF ON OFF Present ISO8201 keywords Msg 1 Msg1 Evacuate the building using the nearest fire exit OFF ON ON Don t Care TEST mode Msg2 Evacuate as directed x2 ON OFF OFF None Wail sou...

Page 4: ...the end of the line If wiring on two branches then two 100k ELDs are used one on each branch The capacitors must be bipolar and their value should be 1 5uF per Watt of their speaker s load see below S...

Page 5: ...esistor from the Isolate switch and blank off the word Isolate on the label ISOL 24V AUTO Yellow LED 2K7 0V EVAC ISOL AUTO ELD 0V EVAC COM A I E Switch Wiring Figure A Isolate Indication via Spare Swi...

Page 6: ...mega 64 Mk3 4100ES 4 Switch SW4 ON for the Master T GEN Fit LK7 in Relay Position for all T GENs 5 FP1600 Omega 64 Mk3 boards have three 7 segment displays 6 ELD value depends upon Input type not fitt...

Page 7: ...to enable Fault Relay Turn SW4 off 3 RRM must be inside FIP and wired to RESP IN 4 Connect wire from NC terminal of relay to S pin of supervision link Do not fit Sup link at all 5 3k3 ELD for MX4428 A...

Page 8: ...L see Note 1 Sigma 5 FP1600 Mk3 Note 3 OMEGA 64 Mk3 Note 3 0V 3 7 Earth Connection The T GEN must be connected to the cabinet EARTH using either the EARTH terminal on the T GEN PCB located beside the...

Page 9: ...upplied fitted to provide a complete functional unit A loom for power control and monitoring is factory fitted The loom is connectorised for direct use with MX1 The connector can be removed and the lo...

Page 10: ...T0186 Issue 2 80 27 July 2012 Page 10 of 10 Manufactured Tyco Fire Protection Products Distributed by 17 Mary Muller Drive PO Box 19 545 by Christchurch New Zealand Tel 64 3 389 5096 Fax 64 3 389 5938...