2/4 

120.515.396.ANZ V1

 

Detector Base Sounder configuration 

The sounder tone and volume are set by a DIL switch. The DIL switch is accessible when the addressable detector is not fitted to the detector base sounder. Positions 1 to 4 set the required tone and 
positions 7 and 8 set the required volume level. Position 6 is used to force the sounder on during commissioning but it remains off during normal operation. 

DIL switch setting positions 1-4 

Tone / volume 

0 0 0 1 

DIN 1 Hz Sweep 

0 0 0 0 

Dutch Slow Whoop 

0 0 1 X 

Temporal 4 

0 1 0 X 

BS 1 Hz Sweep 

0 1 1 X 

March Time Beep 

1 0 0 X 

7 Hz Fast Sweep 

1 0 1 X 

Temporal 3 

1 1 0 X 

2 Tone 

1 1 1 X 

Continuous 970 

DIL switch setting positions 6 - 8 
0 X X 

Normal operation 

1 X X 

SOUNDER ON (test mode) 

X 0 0 

Low Volume 

X 0 1 

Mid Low Volume 

X 1 0 

Mid High Volume 

X 1 1 

High Volume 

Sounder tone and description 

Name 

Tone description 

Pattern 

Frequency (Hz) 

Rate 

DIN 1 Hz Sweep 

Sweep 

1200 to 500 

Falling over 1 s 

Dutch Slow Whoop 

Sweep 

500 to 1200 

Rising over 3.5 s, 0.5 gap 

Temporal 4 

Intermittent 

880 

500 ms On 500 ms Off x 4 then 1 second gap 

BS 1 Hz Sweep 

Sweep 

800 to 970 

1 Hz 

March Time Beep 

Intermittent 

880 

500 ms On 500 ms Off 

7 Hz Fast Sweep 

Sweep 

800 to 970 

142.8 ms ramp, 7 Hz 

Temporal 3 

Intermittent 

880 

500 ms On 500 ms Off x 3 then 1 second gap

 (ISO 8201)

 

2 Tone 

Alternating 

660 / 880 

500 ms per tone 

Continuous 970 

Continuous 

970 

Steady 