TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page
16
of
26
3
Check panel operation on mains supply (Battery
disconnected).
4
Check all connection of panel.
5
Perform WALK TEST mode of panel.
6
Check Smoke Detector.
7
Check siren output.
8
Check battery supply.
9
Check panel mounting screw.
Note
: Please send above servicing report after every 6 months.
2.4.3 Periodic inspection and test of system
For additional information on control panel faults, regular checking of the functionality of the control panel and fire
detection system by a person responsible for fire prevention in the company must ensure the availability of the fire
detection system. Perform the Supervisory & Walk test regularly.
Weekly Testing By The User
▪
Ensure that all indicators are showing correctly.
▪
Check that the internal buzzer are operating correctly.
▪
LCD Display shows messages from the system.
▪
Each week, choose different manual check points so that the manual check points in the building
are tested in rotation over a prolonged period.
▪
Check all detectors and ensure that none are obstructed in any way. Enter results of tests into the
log book.
Quarterly Test
Perform Walk Test / Supervisory Test to check the healthy condition of all zones. After every 3-4
months Walk test must be carried out.
Annual Test
Additionally, test all detectors, check points and check for correct operation.
Every 2 - 3 Years
Clean smoke detectors to ensure correct operation and freedom from false alarms. Special equipment
is required for cleaning smoke detectors.
Every 4 years
Replace sealed lead acid batteries. If the operating temperature exceeds 25
o
C continuously, then the
battery may need to be replaced sooner.