TSFC 12-2 User Manual
Vighnaharta Technologies Pvt. Ltd. Page
17
of
26
2.4.3
Periodic inspection and test of system
For additional information on control panel faults, regular checking of the functionality of the
control panel and fire detection system by a person responsible for fire prevention in the company
must ensure the availability of the fire detection system. Perform the Supervisory & Walk test
regularly.
Weekly Testing By the User
Ensure that all indicators are showing correctly.
Check that the internal buzzer is operating correctly.
LCD Display shows messages from the system.
Each week, choose different manual check points so that the manual check points in the building
are tested in rotation over a prolonged period.
Check all detectors and ensure that none are obstructed in any way. Enter results of tests into the
log book.
Quarterly Test
Perform Walk Test / Supervisory Test to check the healthy condition of all zones. After every 3-4
months Walk test must be carried out.
Annual Test
Additionally, test all detectors, check points and check for correct operation.
Every 2 - 3 Years
Clean smoke detectors to ensure correct operation and freedom from false alarms. Special
equipment is required for cleaning smoke detectors.
Every 4 years
Replace sealed lead acid batteries. If the operating temperature exceeds 25
o
C continuously, then
the battery may need to be replaced sooner.
2.4.4
Pre Check list for call
▪
Check mains supply of system.
▪
Check supply voltage of panel.
▪
Check panel operation on battery backup mode.
▪
Check all Indicators are showing results as per action are taking place in the Panel. Mainly
check out for the system ON indicator is glowing.
▪
LCD display shows messages, buzzer operates.
▪
Check all the cables are connected in proper manner.
▪
Smoke detectors can detect the smoke.
▪
Perform Walk test to ensure all zone are healthy.