TS21I_IR_CO2 User Manual
Vighnaharta Technologies Pvt Ltd Page
7
of
13
Jumpers to set NO/NC contacts for relays
In above picture, there are three jumpers shown
JP1
used to set
Relay1
,
JP2
used to set
Relay2
and
JP3
used to set
Relay3
. Using these jumpers, user can set
NO
type contact or
NC
type of contact.
For
Relay1
JP1
,
Jumper between pin 1 and 2, Relay1 will be
NC
type
Jumper between pin 2 and 3, Relay1 will be
NO
type
JP1
For
Relay2
JP2
,
Jumper between pin 1 and 2, Relay2 output will be
NC
type
Jumper between pin 2 and 3, Relay2 output will be
NO
type
JP2
For
Relay3
JP3
,
Jumper between pin 1 and 2, Relay3 will be
NC
type
Jumper between pin 2 and 3, Relay3 will be
NO
type
JP3
1
2
3
1
2
3
1
2
3
Jumper 2
Jumper 3
Jumper 1