background image

TIHD 932-4

IGNIS - Conventional 4 wire Heat Detector

Product Description: Conventional 4 wire Heat detector IGNIS
is a thermal heat detector that uses a static heat element of 57
°C. It is designed to respond when the convicted thermal
energy
 of a fire increases the temperature of a heat sensitive
element. 

The thermal mass and conductivity of the element regulate the
rate flow of heat into the element. Heat detector operate when
the heat sensitive eutectic alloy reaches the eutectic point
changing state from a solid to a liquid. Thermal lag delays the
accumulation of heat at the sensitive element so that a
fixed-temperature device will reach its operating
temperature
 sometime after the surrounding air temperature
exceeds that temperature.

The range of bases allows adapting the entire line of IGNIS
detectors to the different installation needs. Its ample interior
space makes mounting and electrical connection easier. Its
special double-sided nickel-plated phosphor bronze terminals
guarantee an optimal and reliable long-term contact with the
detector.

Application:

The IGNIS Heat detector is suitable in general applications to
help in the reduction of property damage.
USPs:

RED LED status indication in case of fire.

Respond well to Heat Detection.

Unaffected by wind or atmospheric pressure.

Light weight.

Elegant Design.

Easy Installation.

Make in India design.

Product Features:

Thermal heat Detector model IGNIS.

Available with low profile base and high base with
four 20 mm inputs.

Independent head, bayonet system assembly and
extraction lock.

Nickel-plated phosphor bronze contacts, double-sided
double-grip connection.

SMT Design, High stability.

Wide supply voltage range.

Reverse polarity protection.

360˚ visible RED status LED and output for response
indicator.

ABS thermoplastic material and dust protective cover

Size 100 x 36 (diameter x height)

General specifications

Detection

method

Static Heat Element

Fire Type

Heat

Sensor type

Thermistor

Reset time

15 Sec Maximum

Response

time

10 - 30 Sec

Electrical specifications

Power supply

12Vdc to 30Vdc

Normal

Current

Consumption

15uA at 24V at 25 ˚C (95uA at start-up)

Alarm

Current

20 mA with R=470Ω at 24 V

Environmental specifications

Operating

temperature

-10 ˚C to 70 ˚C

Storage

temperature

-10 ˚C to 80 ˚C

Reviews: