Gas Detection System GDS-24-2/4 User and Installation Manual
Page
16
of
30
3
Panel Wiring
Following figure shows the internal wiring of GDS-24-2.
Figure 7: Internal Wiring of GDS-24-2
Above figure shows the internal wiring diagram of the panel. The AC Mains connections from external supply are
given to power supply. The power supply generates the 24V DC and battery charging voltages that are given to
connector J2 and J7 of CPU PCB respectively. Mains Fail (MF) connections i.e. C and E connections from the
SSM241.2BC are also given to J2.3 (MF) and J2.4 (G) of CPU PCB respectively which is used for detection of AC
fail.
Below figure shows the internal wiring diagram of the panel GDS-24-4. The AC Mains connections from external
supply are given to PCB RASS_1052. Out of two output connections from PCB RASS_1052, one AC mains
connection is given to Power Supply and another mains connection given to PCB RASS_9060. The power supply
generates the 24V DC and battery charging voltages that are given to connector J2 and J7 of CPU PCB
respectively. Two Mains Fail (Mains DI) connections from the PCB RASS_9060 are given to J2 (MF and G) of CPU
PCB which is used for detection of AC fail.