24
Post-Installation Testing
Check list
Please check the following conditions
and correct any deficiencies:
Limit capillaries and sensors
correctly inserted into the sensor
wells?
Electrical connections performed
correctly?
All connections properly connected?
Boiler coding card inserted?
Fuse F2 plugged in?
Outdoor temperature sensor
mounted correctly and cable
connected properly to outdoor
temperature sensor and connector
?
Fixed high limit and adjustable high
limit adjusted properly (if required)?
Labelled appropriate fields on
programming unit according to heat
circuit allocation?
Start-up and adjustments
See Service Instructions
regarding start-up and settings.
Service document ring binder
1.
File Installation, Operating and
Service Instructions in service
binder.
2.
Service box (optional equipment)
now available for service binder.
Technical Data
Rated voltage:
120 VAC
Rated frequency:60 Hz
Rated current:
6 FLA
Power
consumption:
5 W
Certification:
CSA certified
(in conjunction
with a Viessmann
boiler only)
Max. ambient
temperature
during
32 to 104 ºF /
operation:
0 to
40 ºC
For use in living
area and boiler
rooms (normal
ambient conditions)
during storage
and transport:
– 4 to 149 ºF /
–20 to 65 ºC
Relay outputs of Power Pump Module
120 VAC for:
heating circuit
pump
:
3 FLA
*1
DHW production
pump
:
3 FLA
*1
DHW recirculation
pump
:
3 FLA
*1
burner
connector
:
2 FLA
Compiled
fault
indicator
:
3 FLA
*1
connector
:
– two-stage
0.5 FLA
– modulating
0.05 FLA
*1
Total:
max. 9 FLA