28
Vitodens 222-F, B2TB
Application 2 - Operational Setup Instructions
1.
The coding parameters described above are modified
in level 2 coding.
Step1
: To access this coding you must hold the "OK"
key and "Ext. Menu" key together for 5 seconds. This
gives access to the service level.
Step 2
: Hold the "OK" key and "Return" key for 5
seconds. This gives access to level 2 coding.
Notes/Comments
In this system you have a Vitodens 222-F, and a four zone single temperature system. Upon a call for heat,
a zone valve opens turning on the P1(internal) & P3 circulators. In the event there is a call for DHW, the flow
provided by the P1 Circulator will be diverted through the internal plate heat exchanger. This will provide a do-
mestic priority function for the purpose of quickly satisfying a DHW demand. It is recommended to use a vari-
able speed system circulator that will adjust flow based on opening/closing zone valves. If a single speed pump
is being used, ensure a pressure differential bypass is incorporated into the system to avoid “over pumping” a
circuit when a single zone is calling for heat. To setup the boiler for this application you will need
to compete the following:
Type/Option
Step #
Description
Parameter
Set to:
Setup
Location
1
Assign P3 as a heat circuit pump
53:
:02
Set in
Level 2
Coding
2
Configure boiler to operate upon a call for heat
Activates DE1 Contact
3A
:01
Initiates Changeover
D5
:01
Identifies changeover based on DE1 contact
D8
:01
Time limit for changeover
F2
:0
Temperature Limit for disabling changeover
F8
-61
Adjust Daytime schedule
--
Set in
heating
sub menu
Set Reduced room temperature
3ºC
3
Setup HC1 Outdoor Reset Curve
4
Set DHW Temperature
Optional Adjustments
Set a Heating Schedule.
Set in
heating
sub menu
Set an individual DHW Schedule
Configure P1 to shut down once low loss header has reached its setpoint temperature
51:
:01
Set in
Level 2
Coding
Summary of Contents for Vitodens 222-F B2TB
Page 2: ......
Page 4: ...IV ...
Page 10: ...6 ...
Page 14: ...10 Technical Data Vitodens 222 F B2TB 19 and 35 Technical Data ...
Page 29: ...25 Application 1 Operational Setup continued Notes Comments ...
Page 33: ...29 Application 2 Operational Setup continued Notes Comments ...
Page 37: ...33 Application 3 Operational Setup continued Notes Comments ...
Page 41: ...37 Application 4 Operational Setup continued Notes Comments ...
Page 45: ...41 Application 5 Operational Setup continued Notes Comments ...
Page 49: ...45 Application 6 Operational Setup continued Notes Comments ...