22
Fitting location for outside tempera-
ture sensor
■ North or north-westerly wall, 2 to
2.5 m above ground level; in multi
storey buildings, in the top half of the
second floor
■ Not above windows, doors or vents
■ Not immediately below balconies or
gutters
■ Never render over
Outside temperature sensor connec-
tion
2-core lead, length up to 35 m with a
cross-section of 1.5 mm
2
Installation sequence
Electrical connections
(cont.)
5585 174 GB