180
Rated voltage:
230 V~
Rated frequency: 50 Hz
Rated current:
6.0 A
Safety category:
I
IP rating:
IP X 4 D to EN
60529
Permissible ambient temperature
■ During operation:
0 to +40 °C
■ During storage
and transport:
-20 to +65 °C
Electronic tempera-
ture limiter setting:
82 °C (fixed)
Temperature limiter
setting:
100 °C (fixed)
Backup fuse (power
supply):
max. 16 A
Gas boiler, category II
2N3P
Rated heating output range
*2
T
F
/T
R
50/30 °C
kW
12 (17) - 45
12 (17) - 60
Rated heat input range
kW
11.2 (16.1) -
42.2
11.2 (16.1) -
56.2
Power consumption
in the delivered
condition
W
66
122
Connection values
relative to max. load
with
Natural gas E
m
3
/h
4.47
5.95
Natural gas LL
m
3
/h
5.19
6.91
LPG
kg/h
3.30
4.39
Product ID
CE-0085CN0050
Note
The supply values are only for reference (e.g. in the gas contract application) or for
a supplementary, rough estimate to check the volumetric settings. Due to the factory
settings, the gas pressure must not be altered from these values. Reference: 15 °C,
1013 mbar (101.3 kPa).
*2
Values in () when operating with LPG P
Specification
Specification
5585 174 GB