Vitodens 200-W, B2HA 19 to 80 Technical Data
5683 717 - 03
10
Waterside Flow
Waterside Flow (primary circuit)
Supply head pressure (water)
Flow rate
Supply head pressure (water)
Flow rate
Supply head pressure (water)
Flow rate
Pressure drop (primary circuit) for
Vitodens 200-W, B2HA 45, 60
For sizing an on-site circulation system.
Max. flow rate 15.4 USGPM (3500 L/h)
Pressure drop (primary circuit) for
Vitodens 200-W, B2HA 80
For sizing an on-site circulation system.
Max. flow rate 25 USGPM (5700 L/h)
The Vitodens 200-W, B2HA is designed for closed loop,
forced circulation hot water heating systems only. Use
standard friction loss method for pipe sizing. Observe
boiler maximum and minimum flow rate limitations. If
system flow rate exceeds boiler maximum flow rate
(as stated above), falls below the minimum flow rate
or if system flow rate is unknown, Viessmann strongly
recommends the installation of a low-loss header.
An alternative method may be used, such as primary
secondary piping using closely spaced tees.
A low-loss header offers additional benefits not provided
by a pair of closely spaced tees. Viessmann therefore
strongly recommends and prefers the use of a low-loss
header over closely spaced tees. See pages 32 and 33
for low-loss header information. Once the low-loss header
is connected, the built-in low-loss header logic of the
Vitodens 200-W boiler ensures the required
t across the
system through the sensory communication between the
low-loss header and the boiler.
Pressure drop (primary circuit) for
Vitodens 200-W, B2HA 19, 28, 35
For sizing an on-site circulation system.
Max. flow rate: 6.2 GPM (1400 L/h)