background image

Boiler Connections

25

Safety Connections and Pressure Testing

Installing boiler safety devices

Legend

Extension, 2¼”x ¾”
Tee, ¾”
Brass nipple, length 3” x ¾”
Tee, ¾”
Drain valve connection, ¾”
Brass nipple, length 2” x ¾”
Pressure relief valve, ¾” NPT

1.

Remove loosely pre-assembled
combination pressure relief valve and
drain valve assembly.

2.

Apply sufficient amount of pipe
sealant to both ends of all pipe
fittings

,

,

and

, and install

onto tees

and

.

3.

Install pressure relief valve

and

tighten.

4.

Install discharge pipe on pressure
relief valve in such a way that...

H

the end of the pipe is not threaded.

H

the pressure relief discharge pipe
extends to a floor drain and ends
approximately 6” / 150 mm above
the drain.

Ensure that...

H

there is no shutoff valve
installed in the discharge pipe.

H

discharge pipe diameter is not
reduced.

H

discharge is not piped to
outdoors.

Minimum connection diameters:
Pressure relief valve

¾“

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Discharge pipe

¾“

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Piping to precharged
expansion tank

¾“

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Install the (approved) factory supplied
pressure relief valve.

Removal of air from the system must
occur via use of air vent(s) in the
system supply. To ensure the boiler
can be purged of all air, ensure
supply/return water lines do not
contain restrictive piping where air
could be trapped.

Low water cut-off

A low water cut-off may be required by
local codes. If boiler is installed above
radiation level, a low water cut-off
device of approved type (field supplied)
must be installed in all instances. Do
not install an isolation valve between
boiler and low water cut-off (see
subsection entitled “Boiler with low
water cut-off” on page 39 in these
instructions).

5

3

6

9

2

9

7

v

1

.6

Fig. 21

IMPORTANT

Do not install an isolation valve
between boiler and pressure relief
valve.
The discharge pipe for the pressure
relief valve must be oriented to
prevent scalding of attendants.
Pipe pressure relief valve discharge
pipe close to floor drain. Never pipe
discharge pipe to the outdoors.

WARNING

Summary of Contents for Vitodens 200-W 19 WB2B Series

Page 1: ...l mounted gas fired condensing boiler For operation with natural gas and liquid propane gas Heating input 31 to 125 MBH 9 to 37 kW Read and save these instructions for future reference IMPORTANT This...

Page 2: ...Important Regulatory and Installation Requirements in the Installation Instructions Advice to owner Once the installation work is complete the heating contractor must familiarize the system operator u...

Page 3: ...Gas piping pressure test 18 Heating water connections 19 DHW storage tank information 20 Making the DHW connections 20 Accessing the control unit cables 22 Connecting DHW sensor 23 High altitudes sett...

Page 4: ...ogram External heat demand External blocking 48 External 0 10 volt signal connection 48 Connecting the LON communication module 49 Accessory kit connections for heating circuit with mixing valve part...

Page 5: ...sequence Explain the equipment Demonstrate an emergency shut down what to do and what not Explain that there is no substitute for proper maintenance to help ensure safe operation The Maintenance Reco...

Page 6: ...oxide detector with alarm and battery back up may be installed on the next adjacent floor level b In the event that the requirements of this subdivision can not be met at the time of completion of ins...

Page 7: ...tial hazards or important product information Helpful hints for installation operation or maintenance which pertain to the product This symbol indicates that additional pertinent information is to be...

Page 8: ...ural gas For a fuel conversion to liquid propane gas no conversion kit is required Boiler model must be selected based on an accurate heat loss calculation of the building Ensure boiler model is compa...

Page 9: ...obby rooms Garages with workshops Furniture refinishing areas Dry cleaning laundry areas and establishments Auto body shops Refrigeration repair shops Metal fabrication plants Plastic manufacturing pl...

Page 10: ...The Vitodens 200 W WB2B boiler is approved for closet and alcove installation with the following clearances to combustibles Table 1 Clearances Top Front Rear Left Right Vent pipe 0 0 AL CL 0 0 0 0 AL...

Page 11: ...nly Refer to subsequent sections for detailed information on individual piping connections Legend BR Boiler Return NPT BS Boiler Supply NPT BD Boiler Drain CD Condensate Discharge tubing GC Gas Connec...

Page 12: ...see section entitled Wall Mounting on page 13 of this manual for information regarding the installation of the wall mounting bracket The maximum ambient temperature must not exceed 104 F 40 C 1 Heati...

Page 13: ...bracket on each material Skip to the installation instructions applicable to your installation requirements Installation of mounting bracket on brick concrete wall 1 Drill holes 3 8 10 mm using mounti...

Page 14: ...d and metal studs To mount the Vitodens 200 W WB2B boiler on wood or metal studs install mounting bracket on wall as shown in Fig 6 Install mounting bracket on wood studs as per Fig 7 Drill 3 16 pilot...

Page 15: ...behind the control unit flap 2 Loosen the screws at the bottom of the boiler do not remove completely 3 Remove front enclosure panel lift up and pull towards you For installation of the mounting brac...

Page 16: ...through the side wall or the roof taking the shortest possible route and at a rising angle min 3 See Installation Instructions WB2B Venting System for details Proper piping practice Support piping by...

Page 17: ...ip leg and a manual equipment shutoff valve as shown Valves must be listed by a nationally recognized testing agency Make boiler gas connection as shown in Fig 13 3 Perform gas piping pressure test as...

Page 18: ...upply piping system during any pressure testing of that system at test pressures in excess of psig 14 w c 3 Perform leak test Use approved liquid spray solution for bubble test Ensure that no liquid i...

Page 19: ...Boiler Water Return 1 Thoroughly flush heating system particularly before connecting the boiler to an existing system 2 Connect boiler to the heating system Max operating pressure 3 bar 45 psig Test...

Page 20: ...tees as shown for DHW supply and return Apply sufficient amount of thread sealant supplied when making the connections 1 When using a low loss header in the system the DHW connections can be made dow...

Page 21: ...llow the Installation Instructions supplied with the Viessmann DHW storage tank when mounting and securing DHW tank temperature sensor 5369 297 v1 6 Fig 16 Vitocell H 100 DHW storage tank 5 1 IMPORTAN...

Page 22: ...ting cables to the appropriate areas and secure the cables to the control base using existing strain reliefs as shown Legend Low voltage connections 230 VAC connections Communications module accessori...

Page 23: ...her altitude coding card See table 2 or the Viessmann Price List for order information 1 Pull out the existing coding card cut and remove it from the cable tie Insert the high altitude coding card int...

Page 24: ...t a pump with an overflow switch The drain connection must terminate into an open or vented drain as close to the boiler as possible to prevent siphoning of the boiler drain Legend Open or vented fiel...

Page 25: ...meters Pressure relief valve Discharge pipe Piping to precharged expansion tank Install the approved factory supplied pressure relief valve Removal of air from the system must occur via use of air ven...

Page 26: ...ting do not leave boiler unattended 5 Inspect all pipe joint connections and safety devices with a flashlight for leaks A lower manometer reading than 4 bar 60 psig usually indicates loss of water due...

Page 27: ...e field is the responsibility of the heating contractor DHW supply and return piping between boiler DHW connections and the Viessmann DHW tank connections shall be a minimum of 1 pipe size irrespectiv...

Page 28: ...llation of a low loss header Table 3 Typical System Flow Rates Model WB2B 19 26 35 t for NG LPG Output NG LPG MBH 61 85 114 20 F rise GPM 6 1 8 5 11 4 25 F rise GPM 4 9 6 8 9 1 30 F rise GPM 4 1 5 7 7...

Page 29: ...pplied See pages 52 and 56 Installation of H radiator heating circuit high temp circuit H DHW production with the following flow conditions The flow rate of the heating circuit is less than the maximu...

Page 30: ...erature sensor for low loss header P Heating circuit pump 20A See pages 52 and 56 Installation of H radiator heating circuit high temp circuit H DHW production with the following flow conditions The f...

Page 31: ...mp circuit H DHW production with the following flow conditions The flow rate of the heating circuit is less than the maximum possible water flow rate of the Vitodens 200 W WB2B boiler See page 28 for...

Page 32: ...ng circuit high temp circuit H under floor heating circuit with 3 way mixing valve low temp circuit H DHW production with the following flow conditions 1 The water flow rate output of the radiator hea...

Page 33: ...ating pump sA R Low loss header S Viessmann temperature sensor for low loss header T Flow check valve See pages 52 and 56 Installation of different heating circuits H radiator heating circuit high tem...

Page 34: ...rcuit H DHW production with the following flow conditions The total flow rate of the two heating circuits is greater than the maximum possible water flow rate of the Vitodens 200 W WB2B boiler see pag...

Page 35: ...uit with 3 way mixing valve low temp circuit H DHW production with the following flow conditions The total flow rate of the two heating circuits is less than the maximum possible water flow rate of th...

Page 36: ...g circuit pumps Accessory kit for heating circuit with mixing valve 2 Heating circuits with mixing valves I Viessmann temperature sensor for low loss header J Low loss header DHW circulating pump sA D...

Page 37: ...and 8 The boiler control pump logic function must be programmed in the Start up Service Instructions M 5 1 2 5 PRV TPV Alternative location of the expansion tank Fig 31 Note When using a low loss hea...

Page 38: ...ystem of a hot water heating boiler connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation must be equipped with flow control valves or othe...

Page 39: ...e wiring diagram on the boiler enclosure panel Venting Connection Vitodens 200 W WB2B Installation Instructions Venting System 5369 297 v1 6 5369 297 v1 6 Boiler below radiation Vitodens 200 W LWCO Hi...

Page 40: ...mote switching of operating mode H remote disable H alarm output H wall mount base H circulating pump Note on connection of accessories For details regarding other installation steps required please r...

Page 41: ...route cables as illustrated to ensure freedom of movement of control unit 3 Route the cables between the control support console and control unit 4 Secure cables behind the control unit with cable ti...

Page 42: ...heating program changeover terminals 1 2 The allocation of the function external heating program changeover is set via coding address 91 144 External 0 10V signal 145 KM BUS to boiler control board S...

Page 43: ...ctions Legend 40 Power supply s Boiler pump A8 LON cascade communication module X3 Terminal block low loss header sensor outdoor sensor and KM BUS connection X4 KM BUS connection to the Power Pump mod...

Page 44: ...ler pump KM BUS to Power Pump module 5369 297 v1 6 N L 145 144 143 28 L G N L2 N L N L N L 1 2 3 1 2 3 2 3 L1G N 50 20 21 20A 40 N L 120 230 Transformer 145 3 1 2 144 3 1 2 143 3 1 2 40 96 20 35 100 1...

Page 45: ...1 20 40 N L 145 144 143 50 20 21 20A 28 L G N 40 L2 N L N L N L EXTERNAL DEMAND EXTERNAL SIGNAL 0 10 V 120VAC M 120VAC M 120VAC M M 120VAC 120VAC DHW RE CIRC PUMP FAULT ALARM OUTPUT BOILER PUMP DHW PU...

Page 46: ...control board Attach sensors and or KM BUS and or accessories and reinsert the X3 plug Refer to the following sensor information 3 Reinstall the control cover Connecting the low loss header sensor 1...

Page 47: ...th a balcony or gutter The outdoor temperature sensor must not be covered by plaster If mounting on an unplastered wall make allowances for thickness of plaster or remove sensor before plastering wall...

Page 48: ...ing the coding addresses External 0 10 volt signal connection 1 Connect the external 0 10 V signal to plug aVF located in the Power Pump module shown in Fig 45 2 Ensure correct polarity 3 See Fig 46 f...

Page 49: ...e into the Vitotronic 200 H HK1M control board 3 Connect the LON connector cable to the LON module see page 50 See the Vitotronic 200 H HK1M Installation Instructions Installing the LON module to the...

Page 50: ...onnecting the LON communication module continued See the Vitotronic 200 H HK1M Installation Instructions 5369 297 v1 6 40 96 20 35 100 1 2 3 4 5 6 7 X4 X3 L 1 Boiler Control Board GC130 X X11 LON KMK...

Page 51: ...3392 old version See the Mixing Valve Controller Kit for one heating circuit with mixing valve Installation Instructions 5369 297 v1 6 X3 L 1 Boiler Control Board GC130 X11 LON KMK X 8 X 7 LON X2 LON...

Page 52: ...as an alternative for a Vitotronic 050 Dekamatik HK1 control For details on coding and connection to the control please refer to the Vitodens 200 Start up Service Instructions A Mixing valve controlle...

Page 53: ...4 2 C A V 0 3 2 6 1 G W A x 4 System Pump Outside Temperature Sensor Flow Temperature Sensor Low Loss Header Boiler Water Temperature Sensor DHW Temperature Sensor Boiler Pump DHW Pump DHW Re circula...

Page 54: ...l the Vitotronic programming unit 5 Close control unit cover Reinstalling the front enclosure panel 1 Set front enclosure panel on the guide rails and push in place 2 Tighten screws at the bottom Read...

Page 55: ...4 GPM ltr h 6 2 1400 6 2 1400 6 2 1400 Max operating pressure at 210 F 99 C psig bar 45 3 45 3 45 3 Boiler water temperature Adjustable high limit AHL range space heating steady state DHW production F...

Page 56: ...le in 1 1 1 Boiler flue gas connection 8 in mm 23 8 60 23 8 60 23 8 60 Combustion air supply connection coaxial 8 outer in mm 4 100 4 100 4 100 5 Measured flue gas temperature with a combustion air te...

Page 57: ...ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH ITS EQUIVALENT BEFORE SERVICING BOILER OPERATION AFTER SERVICING INTERNAL CONNECTIONS GC130 BURNER IG...

Page 58: ...Sensor DHW Temperature Sensor Ionization Electrode Flue Gas Temperature Sensor Boiler Pump DHW Pump DHW Re circulation Pump Flow Switch Gas Valve Power Supply Fixed High Limit Fault Alarm Output Ignit...

Page 59: ...re or explosion D Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and...

Page 60: ...0 VAC X1 21 pump DHW tank 120 VAC X1 20 pump boiler 120 VAC X1 50 fault alarm 120 VAC X2 28 pump DHW recirculation 120 VAC Total max output current 8A X3 boiler power supply 230 VAC K1 K2 K3 K4 K5 ope...

Page 61: ...61 5369 297 v1 6...

Page 62: ...62 5369 297 v1 6...

Page 63: ...63 5369 297 v1 6...

Page 64: ...smann ca info viessmann ca Viessmann Manufacturing Company U S Inc 45 Access Road Warwick Rhode Island 02886 USA Tel 401 732 0667 Fax 401 732 0590 www viessmann us com info viessmann us com 64 Printed...

Reviews: