18
5600 332 v1.3
Vitodens 100-W, WB1B Installation & Service
Connections
Boiler
Connections
(continued)
Proper piping practice
Gas connection and piping
Support piping by proper suspension method.
Piping must not rest on or be supported by boiler.
Legend
A
Water supply connection
B
Condensate drain connection
C
Gas connection
D
Water return connection
1.
Make gas connection in accordance with codes
CAN/CSA B149.1 or 2 in Canada. In the United
States, use the National Fuel Gas Code ANSI Z223.1/
NFPA 54, as well as local codes where applicable.
2.
Close gas shutoff valve on boiler.
3.
Perform leak test.
4
. Bleed air from gas supply pipe.
See following page for details on gas connection and piping.
2 imperfect threads Use moderate amount of dope
Leave 2 threads bare