34
Two boilers per floor
Rated heating output 24 kW
Number of boilers
2
4
Correction factor (setting value)
Flue length a (m)
0
1
≤15
≤5
2
–
> 5 ≤ 9
3
–
> 9 ≤ 14
4
–
> 14 ≤ 15
5
–
–
6
–
–
Rated heating output 33 kW
Number of boilers
2
4
Correction factor (setting value)
Flue length a (m)
0
1
≤ 9
2
> 9 ≤ 15
≤ 6
3
–
> 6 ≤ 8
4
–
> 8 ≤ 10
5
–
> 10 ≤ 13
6
–
> 13 ≤ 15
Note
The correction factor changes the mod-
ulating range of the boiler.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5675 991 GB
Summary of Contents for Vitodens 050-W BP JD
Page 90: ...90 5675 991 GB...
Page 91: ...91 5675 991 GB...