One boiler per floor
Rated heating output 24 kW
Number of boilers
2
3
4
Correction factor (setting value)
Flue length a (m)
0
1
≤ 21
2
> 21 ≤ 25
≤ 19
≤ 13
3
–
> 19 ≤ 25
> 13 ≤ 17
4
–
–
> 17 ≤ 21
5
–
–
–
6
–
–
–
Rated heating output 33 kW
Number of boilers
2
3
4
Correction factor (setting value)
Flue length a (m)
0
1
≤ 12
2
> 12 ≤ 25
≤ 17
3
–
≤ 16
4
–
> 16 ≤ 20
≤ 14
5
–
> 20 ≤ 25
> 14 ≤ 16
6
–
–
> 16 ≤ 18
Note
The correction factor changes the mod-
ulating range of the boiler.
Commissioning, inspection, maintenance
Further details regarding the individual steps