20
5.
Check the CO
2
content at the upper and lower
heating output again.
If the CO
2
content is not within the specified range:
Repeat steps for upper and lower heating output.
6.
Hold down buttons and
S
simultaneously for lon-
ger than 2 s. Burner switches to operating mode.
Checking the CO content
Enter actual value into the report in the appendix.
Checking the flue gas temperature
Enter actual value into the report in the appendix.
Displaying the ionisation current
Note
The ionisation current can be checked via the burner
control unit. It is
not
possible to check the ionisation
current with a Testomatik-Gas or a multimeter.
0
1.
Hold down
S
for approx. 2 s;
" "
flashes.
0
2.
Press until "5" appears under Service.
0
3.
Press
S
. "5" appears under Status.
0
4.
Press until "3" appears under Service.
0
5.
Press
S
. "3" is shown under Status and during
operation the ionisation current is shown under
Service (e.g. 30 = 3.0
µ
A).
0
6.
Start the burner with emissions test mode enabled
(in control unit menu).
0
7.
Read the ionisation current.
Note
Approx. 2 to 3 s after the gas train has opened
and during operation, the ionisation current should
be at least 3
µ
A.
0
8.
Record the actual value in the report.
0
9.
Hold down
S
for approx. 2 s;
" "
flashes.
10.
Press until "5" appears under Service.
11.
Press
S
. "5" appears under Status.
12.
Press until "0" appears under Service.
13.
Press
S
. The operating display appears again.
Note
The ionisation current can also be checked via the
control unit display. At the same time, modulation can
then take place at the burner control unit.
Service instructions of the control unit
Commissioning, inspection, maintenance
Checking the CO
2
content
(cont.)
5831036