Connections
Fig 11.
Y
Y
Y
Fig 12.
Y
Y
Y
17
Recirculation Connections
H
Pipe domestic hot water supply piping
with tank as illustrated. Connections
must be accessible for service (use
factory supplied adaptors).
Connection sizes are provided in
section entitled Orientation and
Dimensions on page 10.
H
Install recirculation pump, flow check
valve and recirculation timer (for
shut-down during off-hours where
feasible) on the recirculation piping
side.
H
Gravity circulation of the recirculation
system is restricted due to the
upward-curved domestic hot water
discharge piping inside the tank.
H
Connect tank battery to existing
recirculation piping. Cap off unused
recirculation connections of individual
tanks.
H
Saving Energy
A timer on the recirculation pump
reduces the heat loss significantly in
commercial applications during times
when no or reduced demand for
domestic hot water occurs.
Connection of a recirculation system in a multiple tank installation
for systems utilizing boilers or remote heating plants
without
low temperature boiler return water
Drawpoints
Recirculation piping
Circulation pump
Spring-loaded flow check valve
Domestic cold water supply
Domestic hot water supply
Secondary high limit aquastat
location
Connection of a recirculation system in a multiple tank installation
for remote heating plants
with
low temperature boiler return water limit
and/or for multiple recirculation lines
Drawpoints
Recirculation piping
Circulation pump
Spring-loaded flow check valve
Domestic cold water supply
Domestic hot water supply
Secondary high limit aquastat
location
5285
545
v1
.1