23
Note
The cylinder temperature sensor is supplied in the con-
trol unit pack.
3.
4.
1.
2.
AB
AB
B
Fig. 19
A
Sensor wells for 200 l capacity
B
Sensor wells for 400 l capacity
Note
■
Never
wrap insulating tape around the sensor.
■
Secure the sensor on the
outside
of the sensor
retainer contact spring (not in the groove) so that it is
flush with the front of the spring.
■
Insert the sensor retainer with sensor into the sensor
well as far as it will go.
Making the connections on the heating water side
Any number of heating water buffer cylinders, type
SVPA, can be connected in series or in parallel. Pro-
vide connection pipes and air vent valves on site.
!
Please note
The thermal insulation must not come into con-
tact with naked flames.
Exercise caution when welding and brazing.
Installation sequence
Fitting the cylinder temperature sensor
6154032
Installation