7
6020938-02
The electric kit can be installed rapidly:
•
Make sure that all the connected
units are turned off and
disconnected from the system
•
Carry out all connections according
to the instructions related to the
electrical wiring
•
Set the parameters as indicated in
the specific section in the manual of
the Vitocal 100-A unit.
NOTE:
In the case of the 1.2kW electric
heater kit, there is no second electric panel
and no thermowell
Set the parameters as indicated in the Vitocal 100-A unit manual.
All the installation jobs and electric wiring should be done WHEN THE UNIT IS OFF AND
DISCONNECTED FROM THE PLANT
Some units prior to the design of the ACT may require specific parameter settings, and these are
not reported in the supplied manuals. For these requirements, our AFTERSALES department is
ready to provide the necessary assistance.
CAUTION: The electrical wiring to the terminal blocks has to be done only by qualified personnel.
The power supply has to respect the listed limits: failing this, the warranty will terminate
immediately. Before beginning any type of operation, make sure that power is disconnected.
Connect the conductors in order: phase, neutral and earth.
The supply voltage’s fluctuations cannot exceed ±10% of the nominal value. If this tolerance
should not be respected, please contact our technical department.
Install upstream of each unit a suitable protective device and power disconnector, with delayed
characteristic curve, with at least 3 mm contact opening and adequate breaking capacity and
residual current protection.
Effective earthing is mandatory; the manufacturer is not responsible for damage caused in case
of lack thereof.
Use cables that meet the regulations in force in the different countries.
Avoid direct contact with the pipes
ELECTRIC PANEL 1 FOR ACT WITH 2 –3 – 4.5 kW HEATERS – SAFETY THERMOSTATS
A.
Manual reset thermostat:
•
Opening 90±5°C;
•
Manual reset: Remove the front panel, unscrew the plug of
the casing on the thermostats box, press the red button
with a suitable tool, and replace the plug.
B.
Automatic thermostat:
•
Opening 70±4°C;
•
Differential 5±3.5°C.
(CAUTION:
Adjustment knob of the tripping threshold of the
automatic thermostat with factory setting (other values can
Electric panel 1
Electric heater
Cable gland
1
Electric
Panel
2
Thermowell
Cable gland
2