Technical water inertial storage tanks
12
6020938-02
7
INSTALLATION
CAUTION: All the operation described below must be done by QUALIFIED PERSONNEL ONLY.
Before any operation on the unit, make sure that the electric power supply of all the devices on
which they must operate is disconnected.
7.1
GENERAL
When installing the unit, it is necessary to strictly follow the rules listed in this manual, to observe all the
indications and however to take all possible precautions. Failure to comply with the rules reported on this
manual can create dangerous situations.
After receiving the unit, immediately check its integrity. The unit left the factory in perfect
condition; any damage must be immediately reported to the carrier and recorded on the Delivery
Note before signing it.
The company must be informed, within 8 days, of the extent of the damage. The Customer should prepare a
written statement of any severe damage.
CAUTION: The units are designed for outdoor installation. The installation place must be without
any fire risks. Therefore all the necessary measures should be adopted in order to prevent the risk
of fire at the installation place. The outside temperature must never exceed 46°C. Beyond this
value, the unit is no longer covered by the current regulations in the field of safety of pressure
equipment.
CAUTION: The unit must be installed so as to allow free movement for repair and maintenance
operations. The warranty does not cover costs for platforms or other lifting equipment needed for
any interventions.
All the maintenance operations and tests must be done by QUALIFIED PERSONNEL ONLY.
After the maintenance operations, close the panels by fixing them with screws.
7.2
LIFTING AND HANDLING
During unloading and positioning of the unit, utmost care
must be taken to avoid abrupt or violent manoeuvres in
order to protect the internal electronic components. The
units can be lifted by means of a forklift or, in alternative,
with belts, being sure not to damage the side panels and
the cover. It is important to keep the unit horizontal
during these operations.
7.3
POSITIONING AND MINIMUM TECHNICAL CLEARANCES
All the models of the ACT series are designed and built for outdoor installation; for installation, you should
follow the recommended placement and minimum technical clearances given in the table. It is advisable to
create a suitably sized supporting base for the unit.