Troubleshooting
Diagnosis (burner control unit LMO14. ...)
(cont.)
Fault/
characteristics
Flashing
code
red at
LMO14
Cause
Remedy
Burner starts
and flame is
f
d b t
2×
Flame monitor
contaminated
Clean flame monitor
a d a
e s
formed, but
burner cuts
out after safety
2×
Flame monitor receives
insufficient light
Clean sensor plate
out after safety
time expires
2×
Flame monitor faulty
Replace flame monitor
2×
Burner control unit faulty Replace burner control
unit
2×
Carbon deposits on
flame tube or on sensor
plate
Clean flame tube and
sensor plate
Flame
ti
i h
7×
Air in suction line
Seal line and filter
extinguishes
during
7×
Nozzle faulty
Nozzle replacement
during
operation
7×
Burner incorrectly
adjusted
Adjust pre−settings
correctly (see page36)
7×
Sensor plate
contaminated
Clean sensor plate
Ignition
switches ON
d
i
7×
Flame monitor
contaminated
Clean flame monitor
s
tc es O
during
operation
7×
Sensor plate
contaminated
Clean sensor plate
7×
Nozzle contaminated or
faulty
Nozzle replacement
Flame pulsates
Fan pressure too high
Check static burner
pressure via test nipple
on top of fan housing
(U−shaped pressure
gauge). Adjust air
damper or blast tube
connection so that lower
static burner pressure
(see standard values for
burner adjustment,
page36) is not
exceeded.
Oil consumption too
high
Adjust oil pressure
correctly (see page36)
5692589GB
Summary of Contents for VEK
Page 31: ...31 Parts list Parts list cont 5692 589 GB 002 001 017 005 049 009...
Page 33: ...33 Parts list Parts list cont 5692 589 GB 047 020 041 021 040 80o 80p 034 033 046 039 038...
Page 37: ...37 Appendix 5692 589 GB...
Page 39: ...39 Appendix Maint service Maint service Maint service Maint service 5692 589 GB...
Page 41: ...41 Appendix Maint service Maint service Maint service Maint service 5692 589 GB...
Page 42: ...42 Appendix 5692 589 GB...