14
"PROGRAM" operating program
As with the
"AUTO"
operating program, but DHW is
heated during the time phases set in the time program;
see page 15.
DHW heating enabled
Outside temperature from –5 °C to +35 °C
0
DHW temperature in °C
Fig. 14
A
Heat pump
B
Immersion heater
C
DHW temperature achievable with the heat pump
D
Standard DHW temperature (
"AUTO"
)
Outside temperature below –5 °C or above +35 °C
0
DHW temperature in °C
Fig. 15
A
Heat pump
B
Immersion heater
C
DHW temperature achievable with the heat pump
D
Standard DHW temperature (
"AUTO"
)
DHW heating not enabled
Note
The immersion heater is only switched on for frost pro-
tection.
Outside temperature from –5 °C to +35 °C
0
DHW temperature in °C
10
Fig. 16
A
Heat pump
B
Immersion heater
C
DHW temperature achievable with the heat pump
D
Standard DHW temperature (
"PROG"
)
Outside temperature below –5 °C or above +35 °C
0
DHW temperature in °C
10
Fig. 17
A
Heat pump
B
Immersion heater
C
DHW temperature achievable with the heat pump
D
Standard DHW temperature (
"PROG"
)
"NIGHT" operating program
As with the
"AUTO"
operating program, but DHW is
heated between 23:00 and 5:00. The start of DHW
heating is selected so that the standard DHW tempera-
ture is reached at 5:00.
The immersion heater is switched on if the heat pump
cannot reach the standard DHW temperature.
DHW heating
Operating programs
(cont.)
5593131
Summary of Contents for T0E 060-A
Page 5: ...5 10 Keyword index 25 Index Index cont 5593131 ...
Page 26: ...26 5593131 ...
Page 27: ...27 5593131 ...