43
Parameter
Delivered condition
Setting range
Commissioning
Vitovent 300-W air flow rates for maximum air flow rate
300 m
3
/h
"Air Airflow 0"
50 m
3
/h
Do not adjust
"Air Airflow 1"
100 m
3
/h
0 to 300 m
3
/h
"Air Airflow 2"
150 m
3
/h
0 to 300 m
3
/h
"Air Airflow 3"
225 m
3
/h
0 to 300 m
3
/h
Vitovent 300-W air flow rates for maximum air flow rate
400 m
3
/h
"Air Airflow 0"
50 m
3
/h
Do not adjust
"Air Airflow 1"
100 m
3
/h
0 to 400 m
3
/h
"Air Airflow 2"
200 m
3
/h
0 to 400 m
3
/h
"Air Airflow 3"
300 m
3
/h
0 to 400 m
3
/h
Bypass damper
"Bypass temp."
22 °C
12 to 35 °C
"Bypass Hyster."
2 K
0 to 5 K
"Bypass mode"
"AUTO"
"AUTO"
,
"open"
,
"closed"
Pressure imbalance
"Unbalan. Mode"
"ON"
"On"
,
"Off"
"Unbalan. Flow"
0
–
100 to 100 m
3
/h
External electric preheater coil (accessories)
"Extra Heater"
"No ext. Heater"
"No ext. Heater"
,
"ext. Pre-
heater"
,
"Postheater"
CO
2
/humidity sensor (accessories)
"V1 on/off"
0
0 and 1
Note
Never set
2, 3 and 4!
"V1 Vmin"
0 V
0 to 10 V
"V2 on/off"
1
0 and 1
Note
Never set
2, 3 and 4!
"V2 Vmin"
0 V
0 to 10 V
Commissioning/service reports
Appliance settings report
5793 605 GB
Appendix