![Viessmann CVBA Installation Instructions For Contractors Download Page 17](http://html.mh-extra.com/html/viessmann/cvba/cvba_installation-instructions-for-contractors_1016868017.webp)
17
5
Solar collector
6
Boiler
7
Heating circuit
8
Cylinder temperature sensor (on the heating
water side)
9
Fill valve
qP
Temperature sensor, high limit safety cut-out
(STB)
A
C
B
Fig. 17
1.
Install the heat supply control unit.
2.
Check connections
A
and
B
for leaks and
retighten if required.
Tightening torque: 45 to 50 Nm
3. When using copper pipes:
Insert support sleeves
C
supplied.
Tightening torque for both union nuts: 30 Nm
4.
Install the flow line with a rise and fit an air vent
valve at the highest point.
5.
Only for heating water flow temperatures in excess
of 110 °C:
Install a type-tested high limit safety cut-out, if one
has not yet been installed in the system (see
pages 16 and 19). For this, use a temperature
limiter and a high limit safety cut-out.
Connections on the DHW side
■
For the DHW connection, observe DIN 1988 and
DIN 4753 (
c
: SVGW regulations)
■
Connect all pipework with detachable fittings.
■
Seal any connections that are not required with red
brass caps.
■
Equip the DHW circulation pipe with a DHW circula-
tion pump and a check valve.
■
Connection of the DHW circulation pump:
–
Connection to the boiler control unit, provided this
is equipped with a DHW circulation pump connec-
tion.
–
Connection with a time switch, if there is no DHW
circulation pump connection on the boiler control
unit.
Connecting the heating water side and solar side
(cont.)
5838690
Summary of Contents for CVBA
Page 22: ...22 5838690 ...
Page 23: ...23 5838690 ...