11
0
8.
Secure the gas train (without restric-
tor
C
and without rubber cork gas-
ket
D
) with inserted O-ring
B
to
flange
E
; for this, replace the fac-
tory-fitted screws M 5 x 16 with
M 5 x 12 (see separate pack).
0
9.
Tighten screws M 5 x 12 diago-
nally.
Torque: 1.5 Nm.
10.
Secure fitting
A
.
11.
Push compensation hose
G
on to
the gas train.
12.
Affix the enclosed label "Set to ..."
over existing label
F
.
13.
Start the burner (see page 13).
Danger
Escaping gas leads to a risk of
explosion.
Check all fittings for gas tight-
ness.
!
Please note
The use of leak detection spray
can lead to malfunctioning.
Leak detection spray must not
come into contact with electrical
contacts.
Converting to LPG P
Installing the restrictor
BCD
EG
F
A
0
1.
Close the gas shut-off valve.
0
2.
Switch OFF the ON/OFF switch on
the control unit.
0
3.
Switch OFF the mains isolator (out-
side the installation room) or isolate
the mains power and secure against
unintentional reconnection.
0
4.
Undo fitting
A
from the gas supply
pipe.
0
5.
Pull compensation hose
G
from
the gas train.
0
6.
Release the gas train from flange
E
.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5683 757 GB