12
0
7.
Position O-ring
B
, LPG restrictor
C
and rubber cork gasket
D
.
Note
Bevel on the LPG restrictor must
face the gas train.
0
8.
Tighten screws M 5 x 16 diago-
nally.
Torque: 1.5 Nm.
0
9.
Secure fitting
A
.
10.
Push compensation hose
G
on to
the gas train.
11.
Affix the enclosed label "Set to ..."
over existing label
F
.
12.
Check all fittings for tightness.
Danger
Escaping gas leads to a risk
of explosion.
Check all fittings for gas
tightness.
!
Please note
The use of leak detection
spray can lead to malfunc-
tioning.
Leak detection spray must
not come into contact with
electrical contacts.
13.
Start the burner (see page 13).
LPG settings on the burner control unit
C
D
E
F
1.
Press button
S
E
for longer than 2 s.
" "
flashes.
2.
Press button
F
until display
C
shows "6" under Service.
3.
Press button
S
E
until display
C
shows "6" under Status.
4.
Press button
F
until display
C
shows "2" under Status and shows
the current gas type under Service (0
= natural gas or 1 = LPG).
5.
Use button
F
or
D
to select
number "1" for LPG.
6.
Press button
S
E
to confirm. If
applied successfully, display
C
will
briefly show "1" under Service, or
"0" will appear if it failed.
Commissioning, inspection, maintenance