Enamelled DHW cylinder with internal indirect coil for
DHW heating in conjunction with boilers
■
Capacity: 130, 160 and 200 l
■
Suitable for systems conforming to DIN 1988,
EN 12828 and DIN 4753
Inspection and maintenance
DIN 1988 requires a visual inspection and (if neces-
sary) cleaning no later than 2 years after the cylinder
has been commissioned, and thereafter according to
requirements.
Note
We additionally recommend checking the function of
the protective magnesium anode annually. This func-
tion check can be made without interrupting operation
by measuring the earth current with an anode tester
(see page 8).