Check all soldered points and connec-
tions of the refrigerant lines in the
internal device and the external unit
for refrigerant leaks.
Further work on the refrigeration cir-
cuit must only be carried out by a qua-
lified refrigeration engineer.
Checking the condensate drain of the internal device
!
Please note
Accumulations of condensate
can result in equipment
damage.
Ensure that the condensate
drains off correctly.
Fill the condensate pan of the internal
device with water.
Should the water not drain fully
through the drain hose of the internal
device:
&
Check the horizontal level of the
internal device (the condensate pan
must have a slope).
&
Check the drain of the condensate
pan for blockages.
&
Check the drain line. The slope
must be at least 2 % along the entire
drain line.
Checking the free rotation of the external fan
Danger
Unintentional starting of the fan
can lead to severe injuries.
Isolate the unit from the power
supply, check that it is no
longer 'live' and safeguard
against unauthorised recon-
nection.
1.
Remove the front grille from the
external unit.
2.
Turn the fan by hand.
Further details regarding the individual steps
(cont.)
12
Commissioning, inspection, maintenance
5692
689