45
Instantaneous heating water heater power supply 400 V~
N
L1
L2
L3
400 V / 50 Hz
3/N/PE
N2
L1
L2
L3
N1
N3
PE
PE
A
Connection area
B
Jumpers
■ Max. fuse rating 16 A (see specifica-
tion).
■ Low tariff and power-OFF can be
used.
■ Recommended power cable:
5 x 2.5 mm
2
Max. cable length: 25 m
Instantaneous heating water heater power supply 230 V~
230V / 50 Hz
1/N/PE
N
L1
L1
L1
N
N
L1
N1
PE
PE
L1
N1
L1
N1
A
Connection area
B
Jumpers
■ Max. fuse rating 16 A (see specifica-
tion).
■ Low tariff and power-OFF can be
used.
■ Recommended power cable:
7 x 2.5 mm
2
Max. cable length: 25 m
Power supply with power-OFF
Power-OFF without on-site load disconnection
The power-OFF signal is connected
directly to the heat pump control unit.
The compressor will be "forced" OFF
when the power-OFF is active.
Parameter
"Output for instant. heating
water heater at power-OFF 790A"
determines whether and at what stage
the instantaneous heating water heater
stays operational during a power-OFF
period.
Installation sequence
Connecting power cables
(cont.)
5601 574 GB
Installation
Summary of Contents for BWT 221.A06
Page 20: ...20 aCH 10 9 Installation sequence Siting the heat pump cont 5601 574 GB ...
Page 22: ...22 4x 18 21 4x 6x 20 2x 19 Installation sequence Siting the heat pump cont 5601 574 GB ...
Page 23: ...23 25 2x 24 4x 22 23 Installation sequence Siting the heat pump cont 5601 574 GB Installation ...
Page 28: ...28 4 1 3 2 Installation sequence Siting the heat pump cont 5601 574 GB ...
Page 71: ...71 Opening programming unit 2 2x 1 3 Troubleshooting Repairs cont 5601 574 GB Service ...
Page 122: ...122 5601 574 GB ...
Page 123: ...123 5601 574 GB ...