If the power cable needs to be extended:
■ For the electrical installation, observe
the regulations regarding electrical
specifications.
■ For the power cables, use waterproof,
temperature-resistant, well insulated
and hard-wearing cables:
– Cable resistance ≥ 2 MΩ
– Cable cross-section for a connection
length of 2 m: 1 mm
2
Cable cross-section for a connection
length ≥ 2 m: 1.5 mm
2
■ Protect exposed parts with insulating
sheaths to prevent short circuits and
premature ageing of the power cable.
■ Install terminal TB-1503: connect the
cables in accordance with the following
diagram.
N N
L2
L1
L
L
N
A
B
?
C
E D
A
Plug with integral residual current
device
B
PCB in the DHW cylinder
C
Connection, electric immersion
heater
D
Temperature sensor connection
■ When closing the plug, ensure that the
cover only touches the power cable
insulation.
Installation sequence
Electrical connection
5516 344 GB
Installation