1395.1 "Heating limit: Economy function, outside temperature, heating circuit 1"
Setting
Explanations
Heating circuit pump logic function (summer economy
control): Heating circuit pump switches off when out-
side temperature 1 K above selected value. Heating
circuit pump switches back on when outside tempera-
ture 1 K below selected value.
25 °C
25
Delivered condition: Heating limit at outside tempera-
ture 25 °C
10 to 35
Heating limit adjustable from 10 to 35 °C in 1 °C incre-
ments
1396.1 "Heating limit: Economy function, outside temperature, heating circuit 2"
Setting
Explanations
Heating circuit pump logic function (summer economy
control): Heating circuit pump switches off when out-
side temperature 1 K above selected value. Heating
circuit pump switches back on when outside tempera-
ture 1 K below selected value.
25 °C
25
Delivered condition: Heating limit at outside tempera-
ture 25 °C
10 to 35
Heating limit adjustable from 10 to 35 °C in 1 °C incre-
ments
1397.1 "Heating limit: Economy function, outside temperature, heating circuit 3"
Setting
Explanations
Heating circuit pump logic function (summer economy
control): Heating circuit pump switches off when out-
side temperature 1 K above selected value. Heating
circuit pump switches back on when outside tempera-
ture 1 K below selected value.
25 °C
25
Delivered condition: Heating limit at outside tempera-
ture 25 °C
10 to 35
Heating limit adjustable from 10 to 35 °C in 1 °C incre-
ments
Subscriber numbers of connected extensions
All extensions connected to the heat generator (except
the SDIO/SM1A electronics module) must have a sub-
scriber number. The subscriber number is set on rotary
switch S1 at each extension.
System configuration (parameters)
Heating circuit 1, Heating circuit 2, Heating…
(cont.)