36
Danger
CO formation as a result of incorrect burner
adjustment can have serious health implications.
Always carry out a CO test before and after
work on gas appliances.
A
Fig. 24
0
1.
Turn off the ON/OFF switch.
0
2.
Close gas shut-off valve.
0
3.
Undo screw
A
inside test connector on the gas
solenoid valve, but do not remove it. Connect the
pressure gauge.
0
4.
Open the gas shut-off valve.
0
5.
Measure the static pressure and record it in the
report.
Set value: Max. 57.5 mbar (5.75 kPa).
0
6.
Turn on the ON/OFF switch and start the boiler.
Note
During commissioning, the appliance can enter a
fault state if there are airlocks in the gas line.
Reset the appliance after approx. 5 s (see operat-
ing instructions).
0
7.
Measure the supply (flow) pressure. For set val-
ues, see the following table.
Note
Use a suitable measuring device with a resolution
of at least 0.1 mbar (0.01 kPa) to check the supply
pressure.
0
8.
Record the measured value in the report.
Implement measures as indicated in the table
below.
0
9.
Shut down the boiler. Close gas shut-off valve.
Remove pressure gauge. Close test connector
A
with the screw.
10.
Open the gas shut-off valve and start the appli-
ance.
Danger
Gas escaping from the test connector leads
to a risk of explosion.
Check gas tightness at test connector
A
.
11.
Fit front panel (see installation sequence).
Commissioning, inspection, maintenance
Checking the static pressure and supply pressure
6173886