6020930
5.3
POSITIONING AND MINIMUM TECHNICAL CLEARANCES
All models of the Vitocal 100-A range are designed and constructed for outdoor installations.
It is advisable to create an adequately sized support base for the unit. The units transmit a small amount of
vibrations to the ground: it is nonetheless advisable to apply vibration dampers between the base frame
and support surface. It is very important to avoid recirculation between intake and delivery air, so as not to
downgrade performance of the unit or even to interrupt its normal operation.
At least 5 m from the appliance there must be no shafts or manholes where gases might build up
and generate an explosive atmosphere.
This is why the Minimum clearances shown below must be strictly guaranteed.
Do not obstruct or cover the vents on the top cover.
MODEL
A [mm]
B [mm]
C [mm]
D [mm]
E [mm]
AWO-M-AC 101.A06
1500
500
400
400
500
AWO-M-AC 101.A08
1500
500
400
400
500
AWO-M-AC 101.A10
1500
500
400
400
500
AWO-M-AC 101.A12
1500
500
400
400
500
AWO-M-AC 101.A14
AWO-AC 101.A14
1500
500
400
400
500
AWO-M-AC 101.A16
AWO-AC 101.A16
1500
500
400
400
500
MODEL
L [mm]
AWO-M-AC 101.A06
500
AWO-M-AC 101.A08
500
AWO-M-AC 101.A10
500
AWO-M-AC 101.A12
500
AWO-M-AC 101.A14
AWO-AC 101.A14
500
AWO-M-AC 101.A16
AWO-AC 101.A16
500