2.2.2

Technical data

Maximum permitted operating
temperature

95 °C

Minimum permitted operating
temperature

-20 °C 

1)

Maximum permitted operating
pressure

1 MPa (10 bar)

Nominal heating capacity

15 kW

1)

 with anti-freeze added, max. 40 % per cent by volume.

With fluid temperatures below 20 °C, take potential condensation into
consideration. Furthermore, use suitable cooling media if the tempera-
ture of the media drops below the water freezing point.

Materials

Fittings

Pressed brass Ms 58

Pipe runs

Precision pipes

Thermal insulation shell

EPP

Handles

Fibre-glass reinforced, tempera-
ture-resistant plastics

O-rings

EPDM elastomers

Flat seals

AFM 34 or EPDM elastomers

Valve seats

PTFE

Product information

Compact control station preset value

7 from  11

Summary of Contents for 1252.1

Page 1: ...Fonterra radiant heating and cooling central regulation of the supply temperature of several manifolds Model Year built 1252 1 from 01 2012 en_INT Compact control station preset value Instructions for...

Page 2: ...Compact control station preset value 2 from 11...

Page 3: ...Areas of use 6 2 2 Product description 6 2 2 1 Overview 6 2 2 2 Technical data 7 3 Handling 8 3 1 Assembly information 8 3 1 1 Installation dimensions 8 3 1 2 Change supply and return flow section 8 3...

Page 4: ...on does not extend to possible operating instructions The installation of Viega products must take place in accordance with the general rules of engineering and the Viega instructions for use 1 2 Labe...

Page 5: ...or in Germany e g DIN DVGW Some passages in the text may refer to technical codes in Europe Germany These should serve as recommendations in the absence of corresponding national regulations The perti...

Page 6: ...for regulating fixed values without auxiliary energy NOTICE This manual as well as the documents supplied about the circulation pump and the 3 way regulating valve are part of the product and must be...

Page 7: ...below 20 C take potential condensation into consideration Furthermore use suitable cooling media if the tempera ture of the media drops below the water freezing point Materials Fittings Pressed brass...

Page 8: ...1 Sanpress enclosed 3 1 2 Change supply and return flow section The compact control station factory fitted with the supply on the right hand side and the return flow on the left hand side If it is nec...

Page 9: ...ting D as well as the return flow ball valve screw fitting E Rotate the pump with supply ball valve and return flow ball valve by 180 Re tighten screw fittings D and E Re mount the cap B as well as th...

Page 10: ...st place the opening for the mixer approx 53 mm on the left hand side In addition remove the inserted insulating shell for the return flow pipe from the left hand side out of the insulating box and re...

Page 11: ...t of the heat insulation towards the station and clip in the front part of the heat insulation 3 3 Control 3 3 1 Setting the underfloor supply temperature If maximum power nominal power is required se...

Reviews: