![Victron energy SmartSolar MPPT 150/100 Series Manual Download Page 7](http://html.mh-extra.com/html/victron-energy/smartsolar-mppt-150-100-series/smartsolar-mppt-150-100-series_manual_1014743007.webp)
6
The absorption period also ends when the output current of the solar charger
drops to less than 2Amps, not because of low solar array output but because
the battery is fully charged (tail current cut off).
This algorithm prevents over charge of the battery due to daily absorption
charging when the system operates without load or with a small load.
3.6 Configuration of the controller with the rotary switch
Fully programmable charge algorithm (see the software page on our
website) and eight preprogrammed charge algorithms, selectable with a
rotary switch:
Pos
Suggested battery type
Absorption
V
Float
V
Equalize
V
@%I
nom
dV/dT
mV/°C
0
Gel Victron long life (OPzV)
Gel exide A600 (OPzV)
Gel MK
28,2
27,6
31,8
@8%
-32
1
Gel Victron deep discharge
Gel Exide A200
AGM Victron deep discharge
Stationary tubular plate (OPzS)
Rolls Marine (flooded)
Rolls Solar (flooded)
28,6
27,6
32,2
@8%
-32
2
Default setting
Gel Victron deep discharge
Gel Exide A200
AGM Victron deep discharge
Stationary tubular plate (OPzS)
Rolls Marine (flooded)
Rolls Solar (flooded)
28,8
27,6
32,4
@8%
-32
3
AGM spiral cell
Stationary tubular plate (OPzS)
Rolls AGM
29,4
27,6
33,0
@8%
-32
4
PzS tubular plate traction batteries
or OPzS batteries
29,8
27,6
33,4
@25%
-32
5
PzS tubular plate traction batteries
or OPzS batteries
30,2
27,6
33,8
@25%
-32
6
PzS tubular plate traction batteries
or OPzS batteries
30,6
27,6
34,2
@25%
-32
7
Lithium Iron Phosphate (LiFePo
4
)
batteries
28,4
27,0
n.a.
0
Note: divide all values by two in case of a 12V system and multiply by two in
case of a 48V system.