8. SPECIFICATION
Skylla-i
24/80 (1+1)
24/80 (3)
24/100 (1+1)
24/100 (3)
Input voltage (VAC)
230 V
Input voltage range (VAC)
185-265 V
Input voltage range (VDC)
180-350 V
Maximum AC input current @ 180 VAC
16 A
20 A
Frequency (Hz)
45-65 Hz
Power factor
0,98
Charge voltage 'absorption' (VDC)
(1)
28,8 V
Charge voltage 'float' (VDC)
27,6 V
Charge voltage ‘storage’ (VDC)
26,4 V
Charge current (A)
(2)
80 A
3 x 80 A
(max total output: 80A)
100 A
3 x 100 A
(max total output: 100A)
Charge current starter batt. (A)
4 A
n. a.
4
n. a.
Charge algorithm
7 stage adaptive
Battery capacity (Ah)
400-800 Ah
500-1000 Ah
Charge curve, Li-Ion
4 stage, with on-off control or CAN bus control
Temperature sensor
Yes
Can be used as power supply
Yes
Remote on-off port
Yes (can be connected to a Li-Ion BMS)
CAN bus communication port
Two RJ45 connectors, NMEA2000 protocol, galvanically isolated
Synchronised parallel operation
Yes, with the CAN bus
Remote alarm relay
DPST AC rating: 240VAC/4A DC rating: 4A up to 35VDC, 1A up to 60VDC
Forced cooling
Yes
Protection
Battery reverse polarity (fuse) Output short circuit Over temperature
Operating temp. range
-20 to 60°C (Full output current up to 40°C)
Humidity (non condensing)
max 95%
ENCLOSURE
Material & Colour
aluminium (blue RAL 5012)
Battery-connection
M8 bolts
230 VAC-connection
screw-clamp 10mm² (AWG 7)
Protection category
IP 21
Weight kg (lbs)
7 kg (16 lbs)
Dimensions hxwxd in mm
(hxwxd in inches)
405 x 250 x 150 mm
(16.0 x 9.9 x 5.9 inch)
STANDARDS
Safety
EN 60335-1, EN 60335-2-29
Emission
EN 55014-1, EN 61000-6-3, EN 61000-3-2
Immunity
EN 55014-2, EN 61000-6-1, EN 61000-6-2, EN 61000-3-3
1) Output voltage range 20-36V.
Can be set with rotary switch or
potentiometers.
2) Up to 40°C (100°F) ambient.
Output will reduce to 80% at 50°C, and to 60% at 60°C.