3. Installation
• This product should be installed by a qualified electrician.
• During installation ensure that the remote connector with wire bridge is removed (or switch off the remote
on/off switch if installed) to be sure that the inverter cannot be switched on unexpectedly.
3.1. Physical installation
For a dimension drawing of the inverter, see the
of this manual.
3.1.1. Location
To ensure a trouble free operation of the inverter, it must be used in locations that meet the following requirements:
• Avoid any contact with water. Do not expose the inverter to rain or moisture.
• Install the inverter in a dry and well-ventilated area.
• For best operating results, the inverter should be mounted on a flat surface.
• Mount as close as possible to the batteries. Try and keep the distance between the product and the battery to a minimum in
order to minimize cable voltage losses.
• There should be a clear space of at least 10cm around the appliance for cooling. Do not obstruct the airflow around the inverter.
When the inverter is running too hot, it will shut down. When the inverter has reached a safe temperature level, the unit will
automatically restart again.
• Do not place the unit in direct sunlight. The ambient air temperature should be between -20°C and 40°C (humidity <95%
non-condensing). Note that in extreme situations the inverter’s case temperature can exceed 70°C.
• Excessive high ambient temperature will result in a reduced service life, reduced peak power rating or
shutdown of the inverter.
• Never mount the inverter directly above the batteries.
• For safety purposes, this product should be installed in a heat resistant environment if it is used with
equipment where a substantial amount of power is to be converted. You should prevent the presence of e.g.
chemicals, synthetic components, curtains or other textiles, etc., in the immediate vicinity.
3.1.2. Mounting
The inverter is designed to be vertically wall mounted. However, it can also be mounted horizontally or lying down, but these
positions will not offer optimum cooling.
The inverter ships with a wall mounting bracket and 5 screws.
Mount the inverter as follows:
1. Mount the mounting bracket on a wall, using 3 screws.
2. Remove the bottom cover from the inverter.
3. Hang the inverter on the wall mounting bracket.
4. Ensure that the inverter has slotted correctly into the wall bracket.
5. Secure the inverter on the wall using the mounting holes in the bottom right and bottom left of the inverter, using the
remaining 2 screws.
The interior of the product must remain accessible after installation.
3.2. Electrical installation
For a connection overview drawing of the inverter, see appendix
Phoenix Inverter Smart Manual
Page 4
Installation