20
2.3.7.5 3-phase Setting (default: off)
Three identical units can t be interconnected for a 3-phase system, in accordance with
Appendix 0. The batteries must be connected in accordance with Appendix E or F. A
number of settings are then required for each unit.
Firstly, all units must be set for 3-phase operation.
Set the DS 3-7
Switch 3-phase operation on or off
Example
DS-8
DS-7 on
DS-6 on
DS-5
off
DS-4 on
DS-3
off
DS-2
DS-1
Determine whether 3-phase
operation should be on or off.
The default is Off.
The left-hand LED column is for Off.
The right-hand LED column is for
On.
Press the pushbuttons until the
required LED indication is
displayed.
Required: 3-phase operation is
on.
LED indication =
Off
On
One of the three units must be set as the "master" following this setting.. No further settings
are required for the other units.
Set the DS 3-7
Set the master/ slave
Example
DS-8
DS-7
off
DS-6
off
DS-5 on
DS-4 on
DS-3
off
DS-2
DS-1
Determine master or slave.
The default is slave.
The left-hand LED column is for
slave.
The right-hand LED column is for
the master.
Press the pushbuttons until the
required LED indication is
displayed.
Required: this unit is the master.
LED indication =
slave master
Summary of Contents for Phoenix Inverter Series
Page 26: ...24 ...
Page 74: ...20 ...
Page 101: ...3 GB NL F D Appendix B Dimensions ...
Page 102: ...4 ...