4.4.6 Three-phase operation (see appendix D)
The MultiPlus can also be used in 3-phase wye (Y) configuration. To this end, a connection
between the devices is made by means of standard RJ45 UTP cables (the same as for
parallel operation). The system (MultiPlus units plus an optional control panel) will require
subsequently configuration (see Section 5).
Pre-requisites: see Section 4.4.5.
5. CONFIGURATION
Settings may only be changed by a qualified engineer
Carefully read the instructions before changes are made.
Batteries should be placed in a dry and well-ventilated area during charging.
5.1 Standard settings: ready for use
On delivery, the Multi is set to standard factory values. In general, these settings are
suitable for single-unit operation.
Warning: Possibly, the standard battery charging voltage is not suitable for your
batteries! Refer to the manufacturer's documentation or to your battery supplier!
Standard Multi factory settings
Inverter frequency
50 Hz
Input frequency range
45 - 65 Hz
Input voltage range
180 - 265 VAC
Inverter voltage
230 VAC
Stand-alone / parallel / 3-phase
stand-alone
Search mode
off
Ground relay
on
Charger on/ off
on
Battery charge algorithm
four-stage adaptive with BatterySafe mode
Charge current
100% of the maximum charge current
Battery type
Victron Gel Deep Discharge (also suitable
for Victron AGM Deep Discharge)
Automatic equalisation charging
off
Absorption voltage
14.4 / 28.8 / 57,6V
Absorption time
up to 8 hours (depending on bulk time)
Float voltage
13.8 / 27.6 / 55,2V
Storage voltage
13.2 / 26.4 / 52,8V (not adjustable)
Repeated absorption time
1 hour
Absorption repeat interval
7 days
Bulk protection
off
AC input current limit
12A (= adjustable current limit for PowerControl and
PowerAssist functions)
UPS feature
on
Dynamic current limiter
off
WeakAC
off
BoostFactor
2
Programmable relay
alarm function